Choosing the installation location

Outdoor Unit

Where it is not exposed to strong wind.

Well ventilated and dustless places.

Out of the direct sunlight and rain.

Where neighbors are not annoyed by operation sound or hot air.

Solid wall or support that prevents vibration and is strong enough to hold the product weight.

Where there is no risk of flammable gas leakage.

When installing the unit at a high place be sure to fix the unit legs.

3m or more away from the TV or radio (to prevent the screen from being distorted or noise from being generated).

Install the unit horizontally .

Place where drained water does not become any problem.

Place with no plants (especially climbing plants) and where small animal can not access.

Outdoor unit should not be place higher than 2.4m or directly under eaves for accessability for service and OH&S reasons.

• Avoid the following places to prevent malfunction of the unit

- Where there is machine oil

- Salty environment such as seaside areas

- Where sulfide gas exists

- Other special atmosphere areas

ENGLISH

300mm or more

125mm or more

125mm or more

Wrap the refrigerant pipes and the drain hose with the absorbent pad and vinyl tape. Refer to page 43 for further details.

You can select the direction of draining

(left or right).

30 m as maximum pipe length and 3 m as minimum pipe length (It will reduce noise and vibration)

30 meters maximum total pipe length

15 meters maximum total pipe length

Make at least one round: It will reduce noise and vibration

The appearance of the unit may be different from the diagram depending on the model.