Cutting or extending the pipe

5. Check if you flared the pipe correctly (see examples of incorrectly flared pipes below).

Correct

Inclined

Damaged

Cracked

Uneven

 

 

Surface

 

Thickness

6.Align the pipes to connect them easily. Tighten the flare nuts first with your hands, and then with a torque wrench, applying the following torque:

ENGLISH

Flare nut

 

 

 

 

 

 

 

 

 

 

 

Indoor outlet

 

pipe

 

 

 

 

 

Connecting pipe

Outer Diameter

 

Torque

 

 

 

N•m

 

kgf•cm

 

 

 

 

 

 

ø6.35 mm

14~18

 

140~180

ø9.52 mm

34~42

 

350~430

ø12.70 mm

49~61

 

500~620

ø15.88 mm

68~82

 

690~830

• Excessive torque can be cause of gas leakage. If extending pipe by welding/brazing please ensure nitrogen is

used during welding/brazing process. The joint must be accessible and serviceable.

7. For further details on how to connect to the outdoor unit and purge the air, refer to page 39~41.

• Tighten the flare nut with torque wrench according to specified method.

If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

Installing and connecting the drain hose of the indoor unit

When installing the drain hose for the indoor unit, check if condensation draining is adequate. When passing the drain hose through the 65-mm hole drilled in the wall, check the followings:

Wall

Indoor unit

Drain hose

The drain hose must NOT

The end of the drain hose must NOT

slant upwards.

be placed under water.

The drain hose must not be bent.

5cm

less

Keep a clearance of at least 5cm between the end of the drain hose and the ground.

Ditch

Do not place the end of the drain hose in a hollow.

English-37