• Excessive torque can be cause of gas leakage.

• Make the electrical connection and leave the system into“stand by mode”. Do not turn on the system!

This is necessary for better vacuum operation (full OPEN position of Electronic Expansion Valve - EEV -).

3.Connect the charging hose of the low-pressure side of manifold gauge to a gas service port as seen in the picture.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outer Diameter

Torque (kgf•cm)

 

 

 

ø6.35 mm

140~170

 

 

 

 

ø9.52 mm

250~280

 

 

 

 

ø12.70 mm

380~420

 

 

 

 

ø15.88 mm

440~480

 

 

 

 

ø19.05 mm

990~1210

 

 

 

 

ø22.23 mm

990~1210

 

 

Manifold gauge

ENGLISH

4.Open the valve of the low pressure side of manifold gauge counterclockwise.

5.Purge the air in the connected pipes using the vacuum pump for about 15 minutes.

Make sure that pressure gauge shows -0.1MPa(-76cmHg) after about 10 minutes.

This procedure is very important to avoid a gas leak.

Close the valve of the low pressure side of manifold gauge clockwise.

Turn off the vacuum pump.

Check for 2 minutes if there is any pressure change.

Remove the hose of the low pressure side of manifold gauge.

6.Set a valve cork of liquid and gas service port to the open position.

7.Mount the valve stem nuts and the service port cap to the valve, and tighten them at the torque of 183kgf•cm with a torque wrench.

8.Check for a gas leak paying particular attention to the 3-way valve’s stem nuts and to the service port cap (Refer to page 36).

Adding Refrigerant

Add refrigerant charge according to table below:

A 4-meter pipe is supplied with the air conditioner.

If you use a pipe longer than 4 m,

30g of refrigerant R-22 must be added for each extra meter.

If you use a pipe shorter than 4 m,

The purge time is normal.

Refer to the Service Manual for further details.

Valve

Gas service port <Low pressure>

 

Vacuum

Liquid service port

Pump

<High pressure>

(Backward flowing

 

prevention)

 

Valve stem

 

Stem nut

 

A

 

(Gas)

 

B

 

(liquid)

• The remaining air in the Refrigeration cycle, which contains moisture, may cause malfunction on the compressor.

• Always contact the service center or a professional installation agency for product installation.