Samsung UM18B1C2 26,000Btu/h, B-unit, A-unit, Piping length and the height, Circuit breaker, E-30

Models: AM26B1C13 AM27B1C07 AM27B1C13 UM27B1C3 UM26B1C2 UM18B1C2

1 50
Download 50 pages 20.88 Kb
Page 30
Image 30
◗26,000Btu/h

PREPARING THE INSTALLATION

Deciding on Where to Install the Air Conditioner (cont.)

26,000Btu/h

Indoor unit

Outdoor unit

Power supply

Ø, V, Hz

 

 

AM26B1C13

UM26B1C2

1,208-230~,60

 

 

 

Respect the clearances and maximum lengths indicated in the diagram below when installing the unit.

B-unit

12,500 Btu/h

25 mm (1 inch)

or more

A-unit

12,500 Btu/h

100 mm (4 inch) or more

 

600 mm (24 inch)

 

minimum

 

300 mm

300 mm

(12 inch)

(12 inch)

minimum

minimum

 

600 mm

 

(24 inch)

A

minimum

B

 

160 mm (6 inch) or more

A

(15 m (49ft. 3in) maximum)

B

(7 m (23ft) maximum)

Circuit breaker

 

Main power switch

(20A)

 

 

 

 

 

 

 

 

INDOOR UNIT

A

B

OUTDOOR UNIT

E-30

Piping length and the height.

Unit

Pipe size

MAX. piping length

MAX. height

 

Liquid

GAS

A

B

A-unit

1/4"

1/2"

15 m (49ft. 3in)

7 m (23ft)

B-unit

1/4"

1/2"

15 m (49ft. 3in)

7 m (23ft)