Sanyo C0951 Insulation of Refrigerant Tubing, After a tube has been insulated, break or crack

Models: C0951 CL1251 CL1852 CL0951 C1251 C1852

1 22
Download 22 pages 63.33 Kb
Page 17
Image 17
5-5. Insulation of Refrigerant Tubing

5-4. Connecting Tubing between Indoor and Outdoor Units

a)Tightly connect the indoor side refrigerant tubing extend- ed from the wall with the outdoor side tubing. (Fig. 47)

b)To fasten the flare nuts, apply specified torque as:

Table 5

Tube Dia.

Tightening Torque

 

 

1/4" (6.35 mm)

Approx. 130 – 170 lbs.·in. (150 – 200 kg·cm)

 

 

3/8" (9.52 mm)

Approx. 300 – 340 lbs.·in. (350 – 400 kg·cm)

 

 

1/2" (12.7 mm)

Approx. 430 – 470 lbs.·in. (500 – 550 kg·cm)

 

 

5/8" (15.88 mm)

Approx. 520 – 560 lbs.·in. (600 – 650 kg·cm)

 

 

5-5. Insulation of Refrigerant Tubing

IMPORTANT

To prevent heat loss and wet floors due to dripping of con- densation, both tubes must be well insulated with a prop- er insulation material. (Fig. 48) The thickness of the insula- tion should be a minimum 5/16" (8 mm). (Fig. 49)

CAUTION

After a tube has been insulated,

never try to bend it into a narrow

 

 

 

curve, as this may cause the tube to

 

break or crack.

5-6. Taping the Tubes

a)At this time, the 2 refrigerant tubes (and electrical wire if local codes permit) should be taped together with armor- ing tape. The drain hose may also be included and taped together as 1 bundle with the tubing.

b)Wrap the armoring tape from the bottom of the outdoor unit to the top of the tubing where it enters the wall. As you wrap the tubing, overlap half of each previous tape turn. (Fig. 50)

c)Clamp tubing bundle to wall, using 1 clamp approx. every 47 in. (120 cm).

NOTE

Do not wind the armoring tape too tightly, since this will decrease the heat insulation effect. Also, be sure the conden- sation drain hose splits away from the bundle and drips clear of the unit and the tubing.

5-7. Finishing the Installation

After finishing insulating and taping over the tubing, use seal- ing putty to seal off the hole in the wall to prevent rain and draft from entering. (Fig. 51)

Torque wrench

Spanner

Indoor unit

Outdoor unit

Fig. 47

 

Insulation

 

Fig. 48

 

Insulation

Min.

Thickness:

5/16" (8 mm)

min. 5/16" (8 mm)

Fig. 49

Clamp

Insulated tubes

Fig. 50

Apply putty here

Tubing

Fig. 51

17

Page 17
Image 17
Sanyo C0951, C1852 Insulation of Refrigerant Tubing, After a tube has been insulated, never try to bend it into a narrow