12. SERVICE PROCEDURES
2) Air Conditioner does not Operate
1Circuit breaker trips (or fuse blows).
(a)When the circuit breaker is set to ON, it is tripped soon.
•There is a possibility of ground fault.
•Check insulation resistance.
If resistance value is 2 MΩ or less, it is a defect of insulation.
(Example)
Circuit breaker
| 1 |
|
|
|
| |
|
| Outdoor | ||||
|
|
|
| |||
|
|
|
|
| unit | |
|
|
|
|
| ||
|
|
|
| L1 |
| 1 |
| + |
| ||||
|
| L2 |
| 2 | ||
|
|
|
|
| ||
Power | + |
| ||||
| G |
| G | |||
|
|
|
| |||
supply |
|
|
|
| 4 | |
cords |
|
|
|
|
|
|
|
|
|
|
|
|
Ground
2 | 3 |
| |||
Indoor | |||||
|
|
|
| ||
| 4 |
|
| unit | |
+ | + | 1 | |||
| |||||
| |||||
+ |
|
|
| 2 | |
+ | |||||
G | |||||
+ |
| + | |||
4 | |||||
| |||||
power line |
*Set the circuit breaker to OFF.
1Remove power supply cords
from the terminal plate in | NO |
the outdoor unit. |
|
|
•Check insulation resistance of power supply cords.
OK
2Remove
from the terminal plate in | NO | |
the outdoor unit. | ||
| ||
|
•Check insulation resistance of outdoor unit.
OK
3 Remove | NO | |
from the terminal plate in | ||
| ||
the indoor unit. |
| |
|
•Check insulation resistance of indoor unit.
OK
Execute
rewiring.
Insulation of outdoor unit is defective.
Insulation of outdoor unit is defective.
Execute
rewiring.
•Check insulation resistance of electrical parts
in the outdoor unit.
•Check insulation resistance of electrical parts in the indoor unit.