Sanyo SPW-XR254EH56 operation manual

Models: SPW-XR254EH56

1 40
Download 40 pages 52.68 Kb
Page 15
Image 15
Manual background

CAUTION

(1)When linking outdoor units in a network (S-net link system), disconnect the terminal extended from the short plug (CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor units except any one of the outdoor units.

(When shipping: In shorted condition.)

Otherwise the communication of S-net link system is not performed. For a system without link (no con- nection wiring between outdoor units), do not remove the short plug.

(2)Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 3-1)

Outdoor unit

Indoor unit

Outdoor unit

Indoor unit

Outdoor unit

Prohibited

Indoor unit

 

Indoor unit

 

 

 

Fig. 3-1

Prohibited

Indoor unit

(3)Do not install inter-unit control wiring such as star branch wiring. Star branch wiring causes mis-address setting.

Outdoor unit

 

Indoor unit

 

 

 

NO

Indoor unit

 

Fig. 3-2

 

 

Outdoor unit

NO

 

 

Indoor unit

 

 

 

Indoor unit

 

Indoor unit

 

 

 

 

 

Indoor unit

 

Indoor unit

 

 

 

Branch point

 

(4)If branching the inter-unit control wiring, the number of branch points should be 16 or fewer. (Branches less than 1 m are not included in the total branch number.) (Fig. 3-3)

Outdoor unit

Outdoor unit

Outdoor unit

Indoor unit

Branch point

Indoor unit

16 or fewer

more than 1 m

Indoor unit

more than 1 m

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

less than 1 m

Indoor unit

Fig. 3-3

15

Page 15
Image 15
Sanyo SPW-XR254EH56 operation manual