2. HOW TO INSTALL THE INDOOR UNIT
This unit uses a drain pump. Use a carpenter’s level to check that the unit is level.
(1) Fix the suspension bolts securely in the ceiling |
using the method shown in the diagrams (Figs. |
|
| |
Concrete | Insert |
Suspension bolt (M10 or 3/8") (field supply)
support structure, or by any other method that |
ensures that the unit will be securely and safely |
suspended. |
(2) Follow Fig. |
in the ceiling. |
Table |
|
| Unit: mm |
Type | Length | A | B |
| |||
|
|
|
|
25 |
| 820 | 566 |
36, 48 |
| 1,110 | 856 |
Fig.
X
A (Ceiling opening)
B
(Suspention bolt pitch)
Grille center
0038_T_I
Drain hose side
Refrigerant tubing side
1969_X_S
(3)Determine the pitch of the suspension bolts using the supplied
Refrigerant tubing joint (wide tube side)
Suspension lug
E
Fig.
Drain connection (another side) (VP25)
Refrigerant tubing joint (narrow tube side)
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| D |
| |
|
|
|
|
|
|
|
| C |
| |||
|
|
| A | B |
|
| 30 | |||||
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2259_X_S
|
|
|
|
|
| Fig. | |
Table |
|
|
|
|
| Unit :mm | |
Type | Length | A | B | C | D | E |
|
|
| ||||||
|
|
|
|
|
|
|
|
25 |
| 157 | 182 | 261 | 308 | 124 |
|
36, 48 |
| 157 | 182 | 291 | 338 | 124 |
|
5