2-3. Placing the Unit Inside the Ceiling
(1)When placing the unit inside the ceiling, deter- mine the pitch of the suspension bolts using the supplied
Tubing and wiring must be laid inside the ceiling when suspending the unit. If the ceiling is already constructed, lay the tubing and wiring into posi- tion for connection to the unit before placing the unit inside the ceiling.
(2)The length of suspension bolt must be appropri- ate for a distance between the bottom of the bolt and the bottom of the ceiling of 15 mm or more as shown in Fig.
(3)Thread the 2 hexagonal nuts (field supply) and washers onto the 4 suspension bolts as shown in Fig.
Use 2 sets of nuts and washers (upper and lower), so that the unit will not fall off the suspen- sion lugs.
(4)Remove the protective cardboard used to protect the fan parts during transport.
(5)Adjust the distance between the unit and surface of the ceiling. (48 mm) (Fig.
|
|
15 mm or more | (printed on a cardboard packing) |
48 mm | |
|
|
| diagram |
| 2260_X_I |
Fig.
Suspension bolt
Suspension lug
Nuts and washers (Use above and below)
Upper
Lower
Notch
Double nuts
48 mm
2261_X_I
Fig.
6