Sanyo XS1852, C1852 Outdoor Fan does not Run for CL1852, Compressor does not Run

Models: XS1852 CL1852 C1852

1 45
Download 45 pages 15.8 Kb
Page 38
Image 38

11. SERVICE PROCEDURES

6)Outdoor Fan does not Run.

• Check fan rotation.

Rotate the fan gently once or twice by hand.

Check resistance of fan motor winding.

OK

Fan cannot be rotated.

Check fan casing for foreign matter

on the inside.

Fan motor burnout or foreign matter

in bearing.

Remove foreign matter or repair.

Repair or replace.

• Check fan motor capacitor

Check continuity between terminals on the compressor motor magnetic contactor.

7)Outdoor Fan does not Run for CL1852.

Check fuse on PCB Ass’y in

outdoor unit for continuity.

If fuse blows,

• Check resistance of primary

 

winding of transformer.

(TR)

1038_X_S

8)Compressor does not Run.

Check compressor motor capacitor (RC1).

OK

Check resistance of compressor motor winding.

0633_X_S

Wait for 30 minutes until com- pressor has cooled.

Compressor runs.

Compressor internal thermal protector is operated.

Check power supply voltage. Is voltage abnormally low?

NO

Is outdoor heat exchanger coil dirty or are there obstacles near air suction inlet?

1336_X_S

SM830079

– 38 –

Page 38
Image 38
Sanyo XS1852, C1852 service manual Outdoor Fan does not Run for CL1852, Compressor does not Run