930-112-01-B.00 PowerLogicTM EM4800 Series
01/2011 PowerLogic configuration tool
© 2011 Schneider Electric All Rights Reserved 5
Communications Connections If you are configuring the meter at the installation site, see the PowerLogic
EM4800 Series Meter Installation Guide for instructions on connecting the
power. Power connections vary depending on whether the meter is
configured for single-phase or three-phase operation.
If you are pre-configuring the meter in the shop, only Phase A, Neutral, and
protective earth connections are required to power up the PowerLogic
EM4800 Series meter for configuring.
The PowerLogic EM4800 Series Configuration Tool communicates with the
PowerLogic meters through an Ethernet network connection. A network
connection can be accomplished in two ways: either Direct using an Ethernet
crossover cable, or by connecting to a LAN (Local Area Network).
NOTE: If you are attempting to use the list function, the PC being used
to configure the device MUST be on the same network segment as the
PowerLogic meters to be configured. The connect function will allow
the user to find the PowerLogic meters on or off the same segment,
however you must know the correct IP address of the unit being
modified.
Direct Connection Ethernet Requirements
To connect a PC directly to the PowerLogic EM4800 Series meter:
1. Disconnect power from the meter with the installed breaker or
disconnecting device. Use a properly rated voltage sensing device to
confirm power is off.
2. Remove the outer cover.
3. If you are changing parameters that require the programming switch to
be on, remove the inner cover and ensure the programming switches
are in the ON position.
4. Re-install the inner cover.
5. Remove the local LAN Ethernet cable if present and connect the CAT 5
Ethernet cross-over cable between the PC and the PowerLogic
EM4800 Series meter.
6. Restore power to the meter.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow
safe electrical work practices. See NFPA 70E.
This equipment must only be installed and serviced by qualified
electrical personnel.
Turn off all power supplying this equipment before working on or
inside equipment.
Always use a properly rated voltage sensing device to confirm
power is off.
Replace all devices, doors and covers before turning on power to
this equipment.
The meters must be connected to the sense voltage and control
voltage through a properly rated disconnect.
Failure to followthese instructions will result in death or serious
injury.