SCOTSMAN WOOD FURNACE – INSTRUCTION MANUAL
2.7DUCT CONNECTION (Fig S101-5, Fig S101-1)
See figure
The use of A/C coils is not recommended unless special arrangements are made.
Minimum
The furnace must not be installed as a gravity system as the controls are not designed for this type of operation.
The dimensions and locations of permissible openings in casings for ducts, blower, or emergency air are clearly identified on the furnace or on specific templates enclosed in the firebox.
DO NOT use duct elbows having an inside radius of less than 6 in (155mm). Use only 16 x 20 in. duct “S” type interconnection for this furnace.
Make or enlarge the openings in the wood furnace casing exactly as identified for add- on connection and on the appropriate side, trim the furnace insulation flush with cut opening. Fasten edges of insulation securely with metal straps or bend tabs of duct starting collar over insulation edge to hold it in place.
Make all duct connections for the “S” type interconnection (See Fig
CAUTION - The
DO NOT connect to duct work so that a reverse flow is possible. Before attempting installation, determine if there is suitable space available in the furnace area for the furnace connection outlined herein.
The external static pressure in the warm air duct to the house of the original system must be measured prior to any changes to the system. These are to be reset to the same values after the
An important requirement of this type of installation is that when installed in an existing system the main ducts may have to be lowered to assure proper and safe clearances from combustible material. (See Fig
After all connections are made a static pressure test and/or temperature measurement must be made in the outlet plenum of the wood furnace. This is a simple procedure and is outlined as follows using a Dwyer Model 25 or equal inclined manometer:
Drill hole in wood outlet plenum.
Level inclined manometer and adjust to zero, insert manometer tube (Pressure end). With all duct work and doors in place static pressure should measure 0.2 in (50 Pa) with blower running.
Scotsman | 15 |