SCOTSMAN WOOD FURNACE – INSTRUCTION MANUAL
2.4.1COMBUSTION AIR SUPPLY
Air inlets of at least 200 square inches free area (1.5 in2/1000Btu) must be provided to the room occupied by the wood fired or oil fired furnace. These fresh air inlets must provide or allow free access of fresh outside air to the furnace. At no time or under any circumstances can a wood or
The appliance must at all times be able to maintain the approved stack draft. The barometric draft regulator must be installed on the furnace smoke pipe in the same room or at least in such a way that there is unrestricted free passage of air between the combustion air inlet to the furnace or burner and the barometric draft regulator.
It is important to provide adequate combustion air to the furnace. It may be necessary to add a ventilator to an exterior wall of a closed furnace room or an airtight basement.
Operating a wood or oil fired appliance with inadequate combustion air could be hazardous.
2.4.2FLUE PIPE & CHIMNEY
The internal breech baffle should be inserted through the breech towards the front of the furnace until it hits the internal baffle stop. The open slot running the length of the baffle should be located on the top. This baffle is removed during the cleaning procedure. The purpose of the baffle is to prevent
The furnace must be located to meet a minimum venting distance needed between the furnace and the flue. It should also be ducted so that there are a minimum number of elbows used. The flue pipe must be installed with a gradual rise of 1/2” or more per foot from the furnace to the flue.
NEVER ALLOW THE SMOKE PIPE TO RUN DOWNHILL TO THE FLUE!
The smoke pipe and chimney should be at least 7 inches in diameter. The flue pipe or a chimney may be of different
Always meet or exceed flue pipe clearance specifications - 18” clearance from flue pipe to combustibles in all directions.
Connect the furnace only to an approved chimney suitable for solid fuel appliances and capable of venting the products of combustion. The chimney must be installed with proper clearances above roof and from adjacent structures and trees. If a masonry chimney is used it must be in good condition and be equipped with a tile liner. Flue thimble or flue pipe must not extend into the chimney flue, as it will reduce the draft.
Scotsman | 10 |