SECO-LARM USA SA-025EQ manual Remote Alarm Relay Output, Lock Relay Output, Local Alarm Output

Models: SA-025EQ

1 12
Download 12 pages 21.07 Kb
Page 8
Image 8
Remote Alarm Relay Output:

ENFORCER Delayed Egress Timer

Remote Alarm Relay Output:

The SA-025EQ is equipped with a 10A@24VDC Form C dry relay output for a remote alarm.

The remote alarm relay is normally energized. The onboard screen print refers to the energized state as normal.

A remote alarm connected to this output will begin signaling at the start of the pre-delay timer.

The remote alarm will continue signaling until the door is relocked.

In the event of power loss, the remote alarm relay will de-energize to trigger the remote alarm.

The remote alarm will signal when the pre-delay bypass is activated.

The remote alarm will also signal during free egress if the door is left open longer than 5 seconds (door status jumper must be ON for this to occur).

LED 3 (red) is on when the remote alarm relay is energized.

Lock Relay Output:

The SA-025EQ is equipped with a 10A@24VDC Form C dry relay output that can be used with a fail-safe or fail-secure lock.

The lock relay is normally energized. The onboard screen print refers to the energized state as normal.

In standard mode, the lock relay will de-energize after the pre-delay time expires. The lock relay will re-energize when the reset input is activated.

In BOCA mode, the lock relay will de-energize after the pre-delay time expires. The lock relay will re-energize after a door with a N.C. magnetic contact attached to the lock status input has been closed for 30 consecutive seconds.

In timed mode, the lock relay will de-energize after the pre-delay time expires. The lock relay will re-energize after the post-delay time expires.

LED 2 (red) is on when the lock relay is energized.

Local Alarm Output:

The SA-025EQ is equipped with a 500mA@12VDC transistor ground output for a local alarm.

The local alarm output can be set for steady or pulsing by changing jumper 3 (see pg. 7)

LED 4 (red) is on when the local alarm output is active.

Pre-Delay Bypass Input (N.O.+):

Connect a N.O. switch between the pre-delay bypass and the positive terminal.

The pre-delay bypass input bypasses the pre-delay time for immediate egress.

The remote alarm and local alarm outputs are still active when the pre-delay bypass is used.

The door will relock according to the relock mode.