AYXP7FR

Status of

Indication

Malfunction

Content of diagnosis

Inspection location/method

 

Remedy

indoor/

by LED1

No. dis-

 

 

 

 

 

 

outdoor

on out-

played on

 

 

 

 

 

 

units

door unit

main unit

 

 

 

 

 

 

 

*2

display sec-

 

 

 

 

 

 

 

 

tion *1

 

 

 

 

 

 

 

 

Main

Sub-

Main category

Sub-category

 

 

 

 

 

 

cate-

cate-

 

 

 

 

 

 

 

 

gory

gory

 

 

 

 

 

 

Indoor/

6 times

6

-0

Outdoor unit DC

DC overcurrent error

(1)

IPM continuity check

(1)

Replace the outdoor

outdoor

 

 

 

 

 

 

 

 

unit control PWB

units in

 

 

 

 

 

 

 

 

assembly.

complete

 

 

 

 

 

(2)

Check the IPM and heat

(2)

Correct the installa-

shutdown

 

 

 

 

 

 

sink for secure installation.

 

tion (tighten the

 

 

 

 

 

 

 

 

 

screws).

 

 

 

 

 

 

(3)

Check the outdoor unit fan

(3)

Replace the outdoor

 

 

 

 

 

 

 

motor for proper rotation.

 

unit fan motor.

 

 

 

 

 

 

(4)

No abnormality found in

(4)

Replace the outdoor

 

 

 

 

 

 

 

above inspections (1)

 

unit control PWB

 

 

 

 

 

 

 

through (3).

 

assembly.

 

 

 

 

 

 

(5)

No abnormality found in

(5)

Replace the compres-

 

 

 

 

 

 

 

above inspections (1)

 

sor.

 

 

 

 

 

 

 

through (4).

 

 

 

 

 

-1

 

IPM pin level error

 

Check the IPM is attached

 

Replace the outdoor

 

 

 

 

 

 

 

correctly to the outdoor

 

unit control PWB

 

 

 

 

 

 

 

unit control PWB.

 

assembly.

Indoor/

7 times

7

-0

Outdoor unit AC

AC overcurrent error

(1)

Check the outdoor unit air

(1)

Ensure unobstructed

outdoor

 

 

 

 

 

 

outlet for blockage.

 

air flow from the out-

units in

 

 

 

 

 

 

 

 

door unit air outlet.

complete

 

 

 

 

 

(2)

Check the outdoor unit fan

(2)

Check the outdoor unit

shutdown

 

 

 

 

 

 

for proper rotation.

 

fan motor.

 

 

 

-1

 

AC overcurrent error

(1)

IPM continuity check

(1)

Replace the outdoor

 

 

 

 

 

in OFF status

 

 

 

unit control PWB

 

 

 

 

 

 

 

 

 

assembly.

 

 

 

-2

 

AC maximum cur-

(1)

Check the outdoor unit air

(1)

Ensure unobstructed

 

 

 

 

 

rent error

 

outlet for blockage.

 

air flow from the out-

 

 

 

 

 

 

 

 

 

door unit air outlet.

 

 

 

 

 

 

(2)

Check the outdoor unit fan

(1)

Check the outdoor unit

 

 

 

 

 

 

 

for proper rotation.

 

fan motor.

 

 

 

-3

 

AC current defi-

(1)

Check if there is an open-

(1)

Replace the outdoor

 

 

 

 

 

ciency error

 

circuit in the secondary

 

unit control PWB

 

 

 

 

 

 

 

winding of the current

 

assembly.

 

 

 

 

 

 

 

transformer of the outdoor

 

 

 

 

 

 

 

 

 

unit control PWB.

 

 

 

 

 

 

 

 

(2)

Check if the refrigerant

(2)

Charge the specified

 

 

 

 

 

 

 

volume is abnormally low.

 

amount of refrigerant.

 

 

 

 

 

 

(3)

Check if the refrigerant

(3)

Correct refrigerant

 

 

 

 

 

 

 

flows properly.

 

clogs.

 

 

 

 

 

 

 

 

 

(2-way valve, 3-way

 

 

 

 

 

 

 

 

 

valve, pipe, expan-

 

 

 

 

 

 

 

 

 

sion valve)

Indoor/

9 times

9

-0

Outdoor unit

Thermistor installa-

(1)

Check to make sure out-

(1)

Correct the installa-

outdoor

 

 

 

cooling/heating

tion error or 4-way

 

door unit thermistor TH2

 

tion.

units in

 

 

 

switchover

valve error

 

(heat exchanger) and TH5

 

 

complete

 

 

 

 

 

 

(2-way valve) are installed

 

 

shutdown

 

 

 

 

 

 

in correct positions.

 

 

 

 

 

 

 

 

(2)

Measure resistance of

(2)

Replace the ther-

 

 

 

 

 

 

 

thermistors TH1 and TH5.

 

mistor assembly.

 

 

 

 

 

 

(3)

Check the 4-way valve for

(3)

Replace the 4-way

 

 

 

 

 

 

 

proper operation.

 

valve.

 

 

 

 

 

 

(4)

No abnormality found in

(4)

Replace the outdoor

 

 

 

 

 

 

 

above inspections (1)

 

unit control PWB

 

 

 

 

 

 

 

through (3).

 

assembly.

 

 

 

-3

 

Torque control error

(1)

Check if the refrigerant

(1)

Change the specified

 

 

 

 

 

 

 

volume is abnormally low.

 

amount of refrigerant.

 

 

 

 

 

 

(2)

Check the 4-way valve for

(2)

Replace the 4-way

 

 

 

 

 

 

 

proper operation.

 

valve.

 

 

 

 

 

 

(3)

check to see compressor

(3)

Replace the compres-

 

 

 

 

 

 

 

type is correct.

 

sor with the correct

 

 

 

 

 

 

 

 

 

part.

3 – 15

Page 9
Image 9