| AYXP7FR |
|
|
|
|
|
|
|
|
|
Status of | Indication | Malfunction | Content of diagnosis | Inspection location/method |
| Remedy | ||
indoor/ | by LED1 | No. dis- |
|
|
|
|
| |
outdoor | on out- | played on |
|
|
|
|
| |
units | door unit | main unit |
|
|
|
|
| |
| *2 | display sec- |
|
|
|
|
| |
|
| tion *1 |
|
|
|
|
| |
|
| Main | Sub- | Main category |
|
|
|
|
|
| cate- | cate- |
|
|
|
|
|
|
| gory | gory |
|
|
|
|
|
Indoor/ | 2 times | 2 | Cycle tempera- | Compressor high- | (1) Check the outdoor unit air | (1) | Ensure unobstructed | |
outdoor |
|
|
| ture | temperature error | outlet for blockage. |
| air flow from the out- |
units in |
|
|
|
|
|
|
| door unit air outlet. |
complete |
|
|
|
|
| (2) Check if the power supply | (2) | Connect power sup- |
shutdown |
|
|
|
|
| voltage is 90 V or higher at |
| ply of proper voltage. |
|
|
|
|
|
| full power. |
|
|
|
|
|
|
|
| (3) Check the pipe connec- | (3) | Charge the specified |
|
|
|
|
|
| tions for refrigerant leaks. |
| amount of refrigerant. |
|
|
|
|
|
| (4) Measure resistance of the | (4) | Replace the outdoor |
|
|
|
|
|
| outdoor unit compressor |
| unit compressor ther- |
|
|
|
|
|
| thermistor. |
| mistor assembly. |
|
|
|
|
|
| (TH1: Approx. 53 kΩ at |
|
|
|
|
|
|
|
| 25°C) |
|
|
|
|
|
|
|
| (5) Check the expansion | (5) | Replace the expan- |
|
|
|
|
|
| valve for proper operation. |
| sion valve coil, expan- |
|
|
|
|
|
|
|
| sion valve or outdoor |
|
|
|
|
|
|
|
| unit control PWB |
|
|
|
|
|
|
|
| assembly. |
Indoor |
|
|
| Temporary stop due | (Temporary stop for cycle pro- |
| – | |
unit in |
|
|
|
| to compressor dis- | tection) |
|
|
operation |
|
|
|
| charge overheat *3 |
|
|
|
Outdoor |
|
|
| Temporary stop due | (Temporary stop for cycle pro- |
| – | |
unit in |
|
|
|
| to outdoor unit heat | tection) |
|
|
tempo- |
|
|
|
| exchanger overheat |
|
|
|
rary stop |
|
|
|
| *3 |
|
|
|
|
|
|
| Temporary stop due | (Temporary stop for cycle pro- |
| – | |
|
|
|
|
| to outdoor unit heat | tection) |
|
|
|
|
|
|
| exchanger overheat |
|
|
|
|
|
|
|
| *3 |
|
|
|
|
|
|
| Temporary stop due | (Temporary stop for cycle pro- |
| – | |
|
|
|
|
| to | tection) |
|
|
|
|
|
|
| freeze *3 |
|
|
|
Indoor | 3 times | 3 | Dry operation | Temporary stop due | (Temporary stop for cycle pro- |
| – | |
unit in |
|
|
|
| to dehumidifying | tection) |
|
|
operation |
|
|
|
| operation *3 |
|
|
|
Outdoor |
|
|
|
|
|
|
|
|
unit in |
|
|
|
|
|
|
|
|
tempo- |
|
|
|
|
|
|
|
|
rary stop |
|
|
|
|
|
|
|
|
Indoor/ | 5 times | 5 | Outdoor unit | Heat exchanger | (1) Check connector CN8 of | (1) | Correct the installa- | |
outdoor |
|
|
| thermistor | thermistor | the outdoor unit ther- |
| tion. |
units in |
|
|
| cuit error | mistor for secure installa- |
|
| |
complete |
|
|
|
|
| tion. |
|
|
shutdown |
|
|
| Outside tempera- | (2) Measure resistance of out- | (2) | Replace the outdoor | |
|
|
|
|
| ture thermistor | door thermistors TH1 to |
| unit thermistor assem- |
|
|
|
|
| TH5. |
| bly. | |
|
|
|
| Suction thermistor | (3) Check the lead wires of | (3) | Replace the outdoor | |
|
|
|
|
| thermistors TH1 through |
| unit thermistor assem- | |
|
|
|
|
|
| TH5 on the outdoor unit |
| bly. |
|
|
|
|
|
| control PWB for |
|
|
|
|
|
|
|
| cuit. |
|
|
|
|
|
| (4) No abnormality found in | (5) | Replace the outdoor | ||
|
|
|
|
| mistor | above inspections (1) |
| unit control PWB |
|
|
|
|
| error | through (3). |
| assembly. |
|
|
|
| Discharge ther- |
|
|
| |
|
|
|
|
| mistor |
|
|
|
|
|
|
|
| error |
|
|
|
3 – 14