MAINTENANCE

Page 12

 

 

 

When inspecting, check to be certain all hardware and con-

PERIODIC INSPECTION

nections are tight. The principal point of the internal inspection will

 

 

 

be the condition of the arcing contacts on the tapchanger. Since

A sample of oil from the regulator should be subjected to

numerous factors influence the rate of contact tip wear, no one

criteria can be stated to recommend when a contact should be

dielectric breakdown test, per ASTM D-877. If found below

changed.

25kV, the oil should be changed or reconditioned. Refer to

 

ANSI C57.106-2002. Other tests, especially Neutralization

The following figure shows the possible condition of contact wear

Number, Interfacial Tension and Power Factor are also useful

after a period of operation. If the contact surface is less than 1/8

and may be preferred by particular users.

inch wide, the contact should be replaced. (See the Figure below)

 

 

 

The oxidation inhibitor in the oil will be depleted over a period

Contacts, both movable and stationary, show normal burning and wear

of a few years and should be replaced. The inhibitor is 2, 6-

ditertiary-butyl-para-cresol (DBPC) at a concentration level of

once placed in service. If for any reason A1 dimensions exceed 4/5 of

0.2 to 0.3%.

A, the stationary contact should be replaced. (See the Figure below)

The time interval between internal inspections will depend upon frequency of tapchanger operation and the load on the regulator. Regulators subjected to numerous overloads and a high load factor may require more frequent inspections than those carrying normal loads. While internal inspection is not a necessity, preventive maintenance inspections will help assure the continuity of service.

To untank a JFR regulator, proceed as folllows:

1.Remove the regulator from service as described on Page10.

Hazardous voltages. Will cause serious injury, death, or equipment damage.

To prevent:

Always de-energize and ground the equipment before maintenance requiring access to high voltage parts.

A

A1

UPPER FILTER PRESS SEALING

If cover top cap is removed, make certain the cap is properly sealed when replaced on cover. Siemens recommends applying pipe sealant (Loctite PST or equivalent) around the threads of the adapter. Furthermore, it is recommended that the seal be tested by applying 5 psig pressure through the pressure relief valve fitting for 5 minutes, with no loss in pressure. Failure to assure seal may allow moisture to be pulled into the unit during a cool-down cycle.

2.Place the regulator in a position where energized overhead lines will not interfere.

3.Operate pressure relief valve to vent regulator before un- tanking

4.Remove the mounting bolts holding the control box onto the main tank.

5.Remove all cover bolts.

6.The regulator can now be pulled from the main tank by the cover lifting eyes.

FAN MAINTENANCE

Cooling fans (if equipped), require minimum attention. Fans with plain sleeve bearings or Oil-Litesleeve bearings should be oiled at least once a year with SAE 10-W engine oil which does not thicken in cold weather. Oil must be added to sleeve bearings before starting motor for the first time after installation.

Fans equipped with ball bearing motors are packed with grease before shipment and should be greased at least once a year with a soda-soap, ball-bearing grease of medium consistency furnished by a reliable supplier.

Page 16
Image 16
Siemens 21-115532-001 manual Periodic Inspection

21-115532-001 specifications

The Siemens 21-115532-001 is an innovative device designed to enhance operational efficiency across various industrial applications. This equipment embodies the technology and reliability that Siemens is known for, making it a preferred choice among professionals in the field.

One of the primary features of the Siemens 21-115532-001 is its advanced control capabilities. The device integrates seamlessly with existing industrial automation systems, enabling real-time monitoring and control. This allows users to adjust parameters dynamically and respond swiftly to changing operational conditions, ultimately leading to improved productivity and reduced downtime.

The device is equipped with robust communication technologies that facilitate data exchange with other industrial components. This includes compatibility with industry-standard protocols such as Profinet and EtherNet/IP, allowing for smooth integration into diverse ecosystems. The ability to connect with cloud-based systems enhances its functionality, providing valuable insights through data analytics.

In terms of physical characteristics, the Siemens 21-115532-001 is designed for durability. Housed in a rugged casing, it can withstand harsh industrial environments, ensuring longevity and reliability. It is waterproof and resistant to dust, making it suitable for use in outdoor settings or locations with challenging conditions.

The Siemens device also emphasizes safety features. It complies with international safety standards, ensuring that it can be safely integrated into various operations without compromising overall system integrity. This makes it an ideal choice for industries where safety is paramount.

Another significant aspect of the Siemens 21-115532-001 is its user-friendly interface. The device includes intuitive software that simplifies configuration and operation. Users can easily navigate through settings and features, reducing the learning curve and allowing for faster deployment in industrial applications.

In conclusion, the Siemens 21-115532-001 represents a combination of cutting-edge technology, robust design, and operational flexibility. Its advanced features and characteristics make it a vital asset for businesses looking to enhance their industrial processes. With its reliability and efficiency, it stands out as a leading choice in the market for industrial control solutions.