Siemens 21-115532-001 manual Operation At Less Than Rated Voltage, Special Features

Models: 21-115532-001

1 28
Download 28 pages 10.88 Kb
Page 18
Image 18
OPERATION AT LESS THAN

SPECIAL FEATURES

Page 14

OPERATION AT LESS THAN

RATED VOLTAGE

JFR regulators may be operated at less than the voltage for which they were de- signed. All system voltages for which control system taps have been provided are shown on the nameplate. When this is to be accomplished it may be neces- sary to reconnect particular leads at the upper 19-pin terminal block as illustrated on page 5. When operating the regulator at reduced voltage it must be noted that the regulator carries a maximum current rating which rules regardless of the voltage (see table at right). It may therefore be necessary to operate the regulator at less than its nameplate kVA rating.

Units with catalog number starting with:

10 are self cooled

11 are forced-air cooled

Regulators can be modified at factory for 50 Hz operation with appropriate de-rating of voltage.

*Capable of carrying current corresponding to rated kVA when operated at 7200/12470 volts ground wye.

VARI-AMPTMRANGE AND CURRENT RATINGS AVAILABLE

 

±10%

±8 3/4%

±7 1/2%

±6 1/4%

±5%

 

 

220

 

 

 

10-02.5-050.0

200

240

270

320

10-02.5-075.0

300

330

360

405

480

10-02.5-100.0

400

440

480

540

640

10-02.5-167.0

668

668

668

668

668

10-02.5-250.0

1000

1000

1000

1000

1000

10-02.5-333.0

1332

1332

1332

1332

1332

11-02.5-416.3

1665

1665

1665

1665

1665

 

 

110

 

 

 

10-05.0-050.0

100

120

135

160

10-05.0-100.0

200

220

240

270

320

10-05.0-167.0

334

367

401

451

534

10-05.0-250.0

500

550

600

668

668

10-05.0-333.0

668

668

668

668

668

11-05.0-416.3

835

835

835

835

835

 

 

 

 

 

 

10-07.6-038.1

50

55

60

68

80

10-07.6-057.2

75

83

90

102

120

10-07.6-076.2

100

110

120

135

160

10-07.6-114.3

150

165

180

203

240

10-07.6-167.0

219

241

263

296

351

10-07.6-250.0*

328/347

361/381

394/416

443/468

525/555

10-07.6-333.0*

437/463

481/509

524/556

590/625

668/668

10-07.6-416.3*

546/578

601/636

656/668

668/668

668/668

10-07.6-500.0

656

668

668

668

668

10-07.6-667.0

875

875

875

875

875

11-07.6-889.0

1167

1167

1167

1167

1167

10-13.8-069.0

50

55

60

68

80

10-13.8-138.0

100

110

120

135

160

10-13.8-207.0

150

165

180

203

240

10-13.8-276.0

200

220

240

270

320

 

 

 

 

 

 

10-14.4-072.0

50

55

60

68

80

10-14.4-144.0

100

110

120

135

160

10-14.4-288.0

200

220

240

270

320

10-14.4-333.0

231

254

277

312

370

10-14.4-432.0

300

330

360

405

480

10-14.4-576.0

400

440

480

540

640

11-14.4-720.0

500

550

600

668

668

10-14.4-833.0

578

636

668

668

668

 

 

55

 

 

 

10-19.9-100.0

50

60

68

80

10-19.9-200.0

100

110

120

135

160

10-19.9-333.0

167

184

201

226

268

10-19.9-400.0

200

220

240

270

320

10-19.9-667.0

335

368

402

452

536

11-19.9-833.0

418

459

502

565

668

 

 

 

 

 

 