6.2 Parameter of configuration file DOS_CONF.DAT for CP5412-A1

The configuration file DOS_CONF.DAT includes the PROFIBUS-TM bus parameters. A specification of slot coordinates is not necessary.

Bus parameters:

Parameter

l2_ts =

Station No. on PROFIBUS-TM (decimal representation)

 

 

Default setting: 32

 

 

Must be identical to the station address in BATA from

 

 

BR_SYS.INI. If different addresses are entered, the

 

 

parameter 'l2_ts' from DOS_CONF.DAT is used.

 

 

Note: The station addresses should be assigned without gaps

 

 

if possible. This may increase the performance.

Parameter

l2_hsa =

Highest station address on PROFIBUS-TM

 

 

(decimal representation)

 

 

Default setting: 32

 

 

Note: If the actual highest station address is entered exactly,

 

 

this may increase the performance. However, to retain

 

 

a reserve, it is also advisable when configuring to set a

 

 

higher station address than that actually present.

Parameter

l2_ttr =

Token rotation time (decimal representation)

 

 

Default setting: 90000

 

 

The default setting applies to a maximum of 10 active stations

 

 

on the PROFIBUS-TM bus. If more than 10 stations are present

 

 

on the PROFIBUS-TM bus, the parameter must be calculated

 

 

according to the following equation and entered:

 

 

l2_ttr = 9000 * [number of active PROFIBUS-TM stations].

 

 

Note: The factor 9000 in the equation only applies to a baud

 

 

rate of 1.5 MBaud.

All bus parameters are matched to a transmission rate of 1.5 MBaud.

Optimization requires detailed knowledge of the PROFIBUS standard, Part 1, DIN 19245. Selection of a different transmission rate is illegal, and may result in faulty functioning. The bus parameters are described in the SINEC Manual

TF5412/MS-DOS, WINDOWS (C79000-G8976-C031).

Attention: Apart from the bus parameters, the configuration file DOS_CONF.DAT also contains system parameters for handling BRIDGE CS-L2 communication tasks. Unauthorized modifications to these usually result in major faults in the BRIDGE CS-L2.

Note:

The BUS address (BA) cannot be configured in DOS_CONF.DAT .