Product Information |
| February, 1999 |
BRIDGE |
|
|
6.1 Parameter of configuration file BR_SYS.INI | ||
Parameter ADR=xxxx | Address of the | |
| C600 = standard system setting (hexadecimal) | |
Parameter DPR=xx | Address of the register of the TPM 478 | |
| C8 = standard system setting (hexadecimal) | |
Parameter RANGE=xx | Address range of all | |
| coupled over the BRIDGE | |
| Permissible range: | |
| Standard system setting: 20 (hexadecimal) | |
Parameter BATA=xxxx | Definition of the CS address of the BRIDGE in | |
| hexadecimal representation | |
| High byte: | Bus No. BA (hexadecimal) |
| Low byte: | Station No. TA on CS275 bus resp. |
|
| |
Parameter REDUNDANZ=x | Redundancy operating mode of CS275 bus | |
| x = 1: Redundancy on CS275 |
(Standard)
x = 0: No redundancy on CS275
Examples of standard system settings:
TA = 32, BA= 0, Range = 32, TPM478 Slot = 6, REDUNDANZ = 1
____________________________________________________
ADR=C600
DPR=C8
RANGE=20
BATA=0020
REDUNDANZ=1
____________________________________________________
Note:
•The BATA must be set individually for each application. BRIDGE cannot start up with the default factory setting.
•The range is set to its maximum size, i.e. 20h.
•The parameters ADR and DPR correspond to the standard settings of BRIDGE
•If the ‘REDUNDANZ’ parameter is missing in the configuration file, the CS275 bus will operate redundantly.