2-18 9700 POWER METER USER’S GUIDE
Setpoint Framework

This portion of the configuration provided setpoints to monitor phase

current, voltage unbalance and kW sliding window demand. Using

WinPM, upper limits are input for each parameter. If the measur ed value

goes above the specified limit for at least 30 seconds, WinPm annunciates

an alarm.

Displayed/Accessible by Default
Description of
Parameter or Function WinPM MGT
Module
Name Module
Label Output
Register Label
Over kW SW Demand lRelative Setpoint #1 Over kW swd Over kW swd
Over Phase A Current lRelative Setpoint #2 Over I a Over I a
Over Phase B Current lRelative Setpoint #3 Over I b Over I b
Over Phase C Current lRelative Setpoint #4 Over I c Over I c
Over Voltage Unbalance lRelative Setpoint #5 Over V unbal Over V unbal
Nominal kW SW Demand lExternal Numeric #1 kW swd
nominal kW swd
nominal
Nominal Phase A Current lExternal Numeric #2 I a nominal I a nominal
Nominal Phase B Current lExternal Numeric #3 I b nominal I b nominal
Nominal Phase C Current lExternal Numeric #4 I c nominal I c nominal
Nominal Voltage unbalance lExternal Numeric #5 V unbal nominal V unbal nominal
Over-demand monitoring
enable
lExternal Boolean #7 Over kW Enble Over kW Enble
Over-current monitoring
enable
lExternal Boolean #8 Over Amp
Enble Over Amp
Enble
Over-voltage unbalance
monitoring enable
lExternal Boolean #9 Over Vunb
Enble Over Vunb
Enble