International English | Selecting a Drive |
3 Selecting a Drive
Often drive selection is straight forward, as a motor is already installed and the speed range requirement is not excessive. However, when a drive system is selected from first principles, careful consideration may avoid problems in installation and operation, and may also save significant cost.
3.1Overall Considerations
Check the Current rating of the inverter and the motor. Power rating is only a rough guide.
Check that you have selected the correct operating voltage. 230 V
Check the speed range you require. Operation above normal supply frequency (50 or 60 Hz) is usually only possible at reduced power. Operation at low frequency and high torque can cause the motor to overheat due to lack of cooling.
Synchronous motors require
Check overload performance. The inverter will limit current to 150 or 200% of full current very quickly. A standard, fixed speed motor will tolerate these overloads.
Do you need to stop quickly? If so, consider using a braking resistor to absorb the energy. A separate braking unit may be required for some VSDs. See section 0,
Do you need to operate with cables longer than 50m, or screened or armored cables longer than 25m? If so, it may be necessary to
3.2Supply Side Requirements
In order to achieve reliable operation, the main power supply to the inverter system must be suited to the inverter and the anticipated power supplied. The following points should be considered:
3.2.1Supply Tolerance
Inverters are usually designed to operate on a wide range of supply voltages. For example:
Low Voltage units | 200 - 240 V ±10% i.e. | 180 - 264 V | |
High Voltage units | 380 - 480 V | ±10% i.e. | 342 - 528 V |
Very High Voltage units | 500 - 600 V | ±10% i.e. | 450 - 660 V |
Inverters will operate over a wide supply frequency range, typically 47 - 63 Hz
However, many supplies vary outside these voltage levels. For example:
MICROMASTER Applications Handbook | 9 |