Real Applications | International English |
7.4.4Key Parameter Settings
Table | Key Parameters. Conveyor Application | ||
|
|
| |
Number | Value | Meaning | |
|
|
| |
P1120 | 0.6 | Ramp up | |
|
|
| |
P1121 | 0.6 | Ramp down. Fast ramping possible with these settings | |
|
|
| |
P1000 | 003 | Fixed frequency operation | |
|
|
| |
P0003 | 3 | Allows all parameters to be adjusted and set. | |
|
|
| |
P1082 | 110 | Maximum Output Frequency. High speed operation possible in certain | |
|
| circumstances. | |
|
|
|
|
P1060 | 0.3 | Jog | (alternative) ramp up rate |
|
|
|
|
P1061 | 0.3 | Jog | (alternative) ramp down rate |
|
|
| |
P1001 | 40 | Fixed frequency 1 | |
|
|
| |
P1002 | 45 | Fixed frequency 2 | |
|
|
| |
P0701 | 16 | Run at fixed frequency 1 | |
|
|
| |
P0702 | 16 | Run at fixed frequency 2 | |
|
|
| |
P1124 | 16722.2 | Use jog ramp times BiCo Function | |
|
|
| |
P0703 | 99 | Enable BiCo function | |
|
|
| |
P0300- | *** | Settings to suit motor | |
P0311 |
|
|
|
|
|
|
|
By setting P0701 and P0702 to 16, the drive starts and runs to the selected frequency.
42 | MICROMASTER Applications Handbook |