Real Applications | International English |
7.2.3Key Parameter Details
Table
Number | Value | Meaning |
|
|
|
P1000 | 1 | Digital set point preset in MIDIMASTER. Manual adjustment not normally |
|
| required. |
|
|
|
P1040 | 20 | Nominal setpoint |
|
|
|
P0003 | 3 | Allows all parameters to be adjusted and set. |
|
|
|
P1080 | 10 | Minimum fan speed |
|
|
|
P1082 | 30 | Maximum fan speed |
|
|
|
P0778 | 4.00 | Analog output 4 – 20 mA indicating output frequency. This signal is used as |
|
| part of the overall factory management system. Setting P0778 applies a |
|
| 4 mA offset. |
|
|
|
P1300 | 2 | Quadratic V/F curve selected. Selecting the quadratic curve allows a higher |
|
| continuous output, but limits the overload capability, which is not needed in |
|
| this case. The quadratic curve also reduces the power consumption |
|
| because it is optimised for fan and pump applications. |
|
|
|
P0300- | *** | Settings to suit motor |
P0311 |
|
|
|
|
|
P201 | 1 | PID enabled. The following parameters give the best overall stability in this |
|
| particular application. |
|
|
|
P202 | 0.3 | P Gain |
|
|
|
P203 | 0.06 | I Gain |
|
|
|
P204 | 0 | D Gain |
|
|
|
P205 | 1 | Sample Interval |
|
|
|
P206 | 0 | Sensor Filtering |
|
|
|
P207 | 100 | Integral capture range |
|
|
|
P208 | 1 | Sensor type |
|
|
|
P211 | 25 | 0% set point |
|
|
|
P212 | 80 | 100% set point |
|
|
|
P220 | 1 | Switch off at minimum frequency |
|
|
|
P0761 | 2 | PI analog input 4 |
|
|
|
38 | MICROMASTER Applications Handbook |