Device data

Address

Data

Access

 

Parameter

Value range

Default

 

type

 

 

 

 

 

value

0x0300

word [13]

R / O

Device data

 

 

 

 

0x0300

 

 

char SWVersion [11+1]

Software version

 

 

0x0306

 

 

char VDNNr [13+1]

VdN number

 

 

Remote operation

 

 

 

 

 

 

 

 

 

 

 

 

 

Address

Data

Access

 

Parameter

Value range

Default

 

type

 

 

 

 

 

value

0x0400

float

R / O

TEMP

Actual value E3 (unfiltered)

 

 

 

 

 

 

 

 

 

0x0500

word

R / W

REM

Activation remote operation

0...2 *

0

0x0501

word

R / W

ROFF

Controller OFF in REMOTE

0...1 **

0

 

 

 

 

SETPOINT

 

 

0x0502

float

R / W

RHYS1

Switch-on threshold REMOTE

0...-1999

HYS1

0x0504

float

R / W

RHYS2

Switch-off threshold bottom

0...RHYS3

HYS2

 

 

 

 

REMOTE

 

 

0x0506

float

R / W

RHYS3

Switch-off threshold top REMOTE

0...9999

HYS3

0x0508

float

R / W

SPR

Setpoint REMOTE

SPL...SPH

SP1

 

 

 

 

 

 

 

0x050A

word

R / W

RK1

Burner control remote operation

0...1

0

0x050B

word

R / W

RK2

Relay K2 remote operation

0...1

0

0x050C

word

R / W

RK3

Relay K3 remote operation

0...1

0

0x050D

word

R / W

RK6

Relay LK remote operation

0...1

0

0x050E

word

R / W

RSTEP

Step control remote operation

-100...100

0

0x050F

float

R / W

RY

Positioning output remote

0...100

0

 

 

 

 

operation

 

 

* 0 = local

 

 

** 1 = controller OFF

 

 

1 = remote setpoint

 

 

 

 

 

2 = fully remote

 

 

 

 

 

 

10/14