Operating mode | The previous functions of the RWF40... are maintained (apart from memory usage). |
«LOCAL» | The RWF40... can be parameterized and uploaded via the MOD bus, whereby the out- |
| puts cannot be changed. After |
| ating mode «LOCAL». |
Operating mode | The RWF40... monitors cyclic bus communication via the «Dtt» parameter (bus detec- |
«REMOTE SETPOINT» | tion timer). Operating mode «REMOTE SETPOINT» is active as long as the bus calls |
| within the predefined period of time. If the time limit is crossed, the RWF40... will switch |
| to operating mode «LOCAL» and continues to operate using the parameters of local |
| operation. |
| Like in operating mode «LOCAL», the control functions of the RWF40... are maintained. |
| With regard to setpoint and switching thresholds, only «RSP» and «RHYS1...RHYS3» |
| are active. The setpoints (SP1 and SP2), the external setpoint, the weather- |
| compensated setpoint, the analog / binary setpoint shift and the associated changeover |
| functions are not available. |
| After the controller’s |
| «Hys1...Hys3» will be copied to RAM as remote parameters in a |
| These remote parameters can then only be changed via the management system. |
| The control algorithm can be deactivated by the management system via parameter |
| «ROFF=1». In that case, the RWF40... will switch the burner off and causes the con- |
| trolling element to travel to the fully closed position. The controller terminates manual |
| operation (analog safety shutdown). |
| |
| The management system controls contact «RK6» (relay «K6»). |
Operating mode | The RWF40... monitors cyclic bus communication via the «Dtt» parameter (bus detec- |
«FULLY REMOTE» | tion timer). Operating mode «FULLY REMOTE» is active as long as the bus calls within |
| the predefined period of time. If the time limit is crossed, the RWF40... will switch to |
| operating mode «LOCAL» and continues to operate using the parameters of local op- |
| eration. |
| The management system switches the burner (RK1, relay «K1»), controls the actuator |
| (RK2 and RK3, relays «K2 / K3»), or defines the degree of modulation in the case of an |
| analog output, and controls contact «RK6» (relay «K6»). |
| Using parameter «ROFF=1», control of the burner and controlling element can be |
| switched off by the management system. In that case, the RWF40... deactivates the |
| burner and causes the controlling element to travel to the fully closed position. |
| Manual operation and |
| |
| If, with a |
| are «K2 = deenergized» and «K3 = energized» (closing). |
| The analog output is set as follows, depending on the relay positions «RK2» and |
| «RK3»: |
| K2 = energized, K3 = deenergized analog output = 10 V or 20 mA |
| K2 = deenergized, K3 = energized analog output = 0 V or 0 / 4 mA |
| Setting the «RY» by the management system has no impact. |