The transmission mode used is the RTU (remote terminal unit) mode. Data are trans- mitted in binary format (hexadecimal) with 8 bits.

The LSB (least significant bit) is transmitted first. ASCII mode is not supported.

Data format

The data format describes the structure of the transmitted byte.

 

 

 

 

 

 

 

Data word

Parity bit

Stop bit ½ bit

Number of bits

 

8 bit

Not

1

9

Device address

The slaves’ device addresses can be selected between 1 and 99.

Device address 0 is reserved.

￿A maximum of 31 slaves can be addressed via the RS-422 / RS-485 interface.

There are 2 choices of data exchange:

Query

Data query / instructions delivered by the master to a slave via the re-

 

spective device address.

 

The addressed slave responds.

Broadcast

Master instructions to all slaves via device address 0.

 

The addressed slaves do not respond.

 

A data query with device address 0 does not make sense.

 

A certain setpoint can be transmitted to all slaves, for example.

 

In that case, correct adoption of the value by the slaves should be

 

checked by subsequent setpoint readout.

2/14

Siemens Building Technologies

CC1A7865.1en

HVAC Products

31.10.2002