Siemens RS-485 manual Address tables, Address Data Access Parameter Value range Default

Models: RS-485

1 14
Download 14 pages 12.8 Kb
Page 9
Image 9

Address tables

Process data

 

Address

 

Data

Access

 

Parameter

Value range

Default

 

 

 

 

type

 

 

 

 

value

 

 

0x0000

 

float

R / O

 

Actual value E1

 

 

 

 

0x0002

 

float

R / O

 

Actual value E2

 

 

 

 

0x0004

 

float

R / O

 

Actual value E3

 

 

 

 

0x0006

 

float

R / W

 

Current setpoint

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x0008

 

float

R / W

SP1

First setpoint

SPL...SPH

0

 

 

0x000A

 

float

R / W

SP2 (=dSP)

Second setpoint

SPL...SPH

0

 

 

Parameter level

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Address

 

Data

Access

 

Parameter

Value range

Default

 

 

 

 

type

 

 

 

 

value

 

 

0x000C

 

float

R / W

AL

Limit value limit comparator

-1999...9999

0

 

 

0x000E

 

float

R / W

Pb1

Proportional band

0.1...9999

10

 

 

0x0010

 

float

R / W

dt

Derivative action time

0...9999

80

 

 

0x0012

 

float

R / W

rt

Integral action time

0...9999

350

 

 

0x0014

 

float

R / W

db

Dead band (neutral zone)

0.0...100.0

1

 

 

0x0016

 

float

R / W

tt

Actuator running time

10...3000

15

 

 

0x0018

 

float

R / W

Hys1

Switch-on threshold

0...-199.9

-5

 

 

0x001A

 

float

R / W

Hys2

Switch-off threshold, bottom

0...Hys3

3

 

 

0x001C

 

float

R / W

Hys3

Switch-off threshold, top

0.0...999.9

5

 

 

0x001E

 

float

R / W

q

Reaction threshold

0.0...999.9

0

 

 

0x0020

 

float

R / W

H

Heating curve slope

0.0...4.0

1.0

 

 

0x0022

 

float

R / W

P

Parallel displacement

-90...90

0

 

 

 

 

 

 

 

room temperature

 

 

 

 

Configuration level

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Address

 

Data

Access

 

Parameter

Value range

Default

 

 

 

 

type

 

 

 

 

value

 

 

0x0024

 

char [4]

R / W

C111

 

 

9030

 

 

0x0026

 

char [4]

R / W

C112

 

 

0010

 

 

0x0028

 

char [4]

R / W

C113

 

 

0110

 

 

0x002A

 

char [4]

R / W

C000

 

 

0000

 

 

 

 

 

 

 

 

 

 

 

 

0x002C

 

float

R / W

SCL

Normalization start value: Input 1

-1999...9999

0

 

 

0x002E

 

float

R / W

SCH

Normalization end value: Input 1

-1999...9999

100

 

 

0x0030

 

float

R / W

SCL2

Normalization start value: Input 2

-1999...9999

0

 

 

0x0032

 

float

R / W

SCH2

Normalization end value: Input 2

-1999...9999

100

 

 

0x0034

 

float

R / W

SPL

Start value setpoint limitation

-1999...9999

0

 

 

0x0036

 

float

R / W

SPH

End value setpoint limitation

-1999...9999

100

 

 

0x0038

 

float

R / W

OFF1

Offset input 1

-1999...9999

0

 

 

0x003A

 

float

R / W

OFF2

Offset input 2

-1999...9999

0

 

 

0x003C

 

float

R / W

OFF3

Offset input 3

-1999...9999

0

 

 

0x003E

 

float

R / W

HYST

Hysteresis of limit comparator

0...9999

1

 

 

0x0040

 

float

R / W

df1

Filter time constant input 1

0.0...100.0

1.0

 

 

0x0042

 

float

R / W

dF3

Filter time constant input 3

0...1440

1278

 

 

0x0044

 

float

R / W

dtt

Bus detection timer

0...7200 *

30

 

 

0x0046

 

float

R / O

oLLo

Start value actual value limit

-1999...9999

-1999

 

 

0x0048

 

float

R / O

oLHi

End value actual value limit

-1999...9999

9999

 

 

 

 

 

 

 

* Timer = 0 means switched off

 

 

 

 

 

 

 

 

 

This parameter can only be changed via the management system

 

 

 

 

 

 

 

 

 

9/14

 

 

 

 

 

 

 

 

 

 

 

Siemens Building Technologies

 

 

 

CC1A7865.1en

 

 

HVAC Products

 

 

 

 

 

31.10.2002

 

Page 9