Programming FCs (Functions) and FBs for S7 Ethernet CPs
166 SIMATIC NET NCM S7 for Industrial Ethernet
C79000-G8976-C129–06
Table 5-3 AG_RECV / AG_LRECV Codes
NDR MeaningSTATUSERROR
0 1 8304HThe connection is not established. The send job should only be
attempted again after waiting for at least 100 ms.
0 1 8F23HSource area invalid, for example:
Area does note exist in the DB.
0 1 8F25HArea error writing a parameter.
0 1 8F29HAlignment error writing a parameter.
0 1 8F30HParameter is in the write-protected 1st act. data block.
0 1 8F31HParameter is in the write-protected 2nd act. data block.
0 1 8F32HParameter contains a DB number that is too high.
0 1 8F33HDB number error.
0 1 8F3AHDestination area not loaded (DB).
0 1 8F43HTimeout writing a parameter to the I/O area.
0 1 8F45HAddress of the parameter to be read is disabled in the access
track.
0 1 8F7FHInternal error, e.g. illegal ANY reference.
0 1 8090HNo module with this address exists or the CPU is in the STOP
mode.
0 1 8091HLogical base address not at a double word boundary.
0 1 8092HIn the ANY reference, a type other than BYTE is specified.
(S7-400 only)
0 1 80A0HNegative acknowledgment reading from the module.
0 1 80A4HThe communication bus connection between the CPU and CP is
not established.
0 1 80B0HThe module does not recognize the data record.
0 1 80B1HDestination area invalid.
0 1 80B2HThe communication bus connection between the CPU and CP is
not established.
0 1 80C0HThe data record cannot be read.
0 1 80C1HThe specified data record is currently being processed.
0 1 80C2HThere are too many jobs pending.
0 1 80C3HCPU resources (memory) occupied.
0 1 80C4HCommunication error (occurs temporarily and a repetition in the
user program will often remedy the problem).
0 1 80D2HModule base address incorrect.