Programming FCs (Functions) and FBs for S7 Ethernet CPs
158 SIMATIC NET NCM S7 for Industrial Ethernet
C79000-G8976-C129–06
Table 5-2 AG_SEND / AG_LSEND Codes
DONE MeaningSTATUSERROR
0 1 8F7FHInternal error, e.g. illegal ANY reference.
e.g. parameter LEN=0
0 1 8090HNo module with this address exists or the CPU is in the STOP
mode.
0 1 8091HLogical base address not at a double word boundary.
0 1 8092HIn the ANY reference, a type other than BYTE is specified.
(S7-400 only)
0 1 80A4HThe communication bus connection between the CPU and CP is
not established. (Only with newer CPU versions)
0 1 80B0HThe module does not recognize the data record.
0 1 80B1HThe specified length (in the LEN parameter) is incorrect.
0 1 80B2HThe communication bus connection between the CPU and CP is
not established.
0 1 80C0HThe data record cannot be read.
0 1 80C1HThe specified data record is currently being processed.
0 1 80C2HThere are too many jobs pending.
0 1 80C3HCPU resources (memory) occupied.
0 1 80C4HCommunication error (occurs temporarily and a repetition in the
user program will often remedy the problem).
0 1 80D2HModule base address incorrect.