Slant/Fin B-200A Bobcat Boiler Display Board, “Boiler Operation Status”, Lockout Alarm condition

Models: B-200A B-120A

1 12
Download 12 pages 32.3 Kb
Page 9
Image 9
9Bobcat Model B-120A and B-200A

9Bobcat Model B-120A and B-200A

Table 1

 

Bobcat Boiler Display Board

Table 1

Table 3

 

 

Table 3“Boiler Operation Status”

Table 2

Table 1

Table 3

 

Mode

 

Description & Temperature Display

 

Display

 

 

 

 

Boiler is on stand-by mode.

 

 

Temperature display shows supply water Temp.

 

 

Space heating mode.

 

 

Temperature display shows supply water Temp.

 

 

Domestic hot water mode.

 

 

Temperature display shows supply waterTemp.

 

 

Frost protection mode.**

 

 

Temperature display shows supply water Temp.

Lockout (Alarm) condition.

Temperature Display indicates the lockout code

Reset button must be pressed to resume normal operation.

Error Condition. *

Temperature display indicates the error code.

Warning Condition. ***

Temperature display indicates the error code.

Table 1

Note:

Blinking dot on “Mode Display” indicates active heating control, burner off. Steady dot indicates burner is on.

*: Error must be corrected to resume boiler operation. Pressing the “Reset” button is not required.

**: The boiler circulator is energized, when boiler water temperature drops below 50˚F.

***: Error must be corrected to resume DHW operation. Space heating not affected. Pressing the “Reset” button is not required.

Page 9
Image 9
Slant/Fin B-200A Bobcat Boiler Display Board, “Boiler Operation Status”, Lockout Alarm condition, Error Condition, Mode