11 | Bobcat Model |
DIAGNOSTIC ERROR CODES
WARNING:
If an operational problem has occurred, the boiler will shut off and show an “A”, “E” or “H” in the mode display, along with an error code in the temperature display.
Do not attempt performing any service under these conditions, but do note the mode and temperature dis- play indication, in case the problem clears itself. An “A” indication error can be cleared by pressing the reset button once, which will allow
A.LOCKOUT ERRORS:
Indicated by an “A” in the mode display. The reset button must be pressed to clear the error and retry operation. The temperature display shows the error code.
ERROR | INDICATION | |
CODE | ||
| ||
01 | Ignition Failure - 3 unsuccessful ignition | |
attempts in a row | ||
| ||
|
| |
02 | Flame Failure - 3 losses of flame signal | |
during one demand | ||
| ||
|
| |
03 | Water High Limit Open | |
|
| |
04, 05, 09, |
| |
10, 12, 13, | Control Failure | |
14, 15, 16, | ||
| ||
18, 32 |
| |
|
| |
19, 20 | Flame Detected at Wrong Time | |
|
| |
33 | Fan Failure - RPM Error | |
|
|
ERROR | INDICATION | |
CODE | ||
| ||
01 | Water Outlet Sensor Open | |
|
| |
02 | Water Inlet Sensor Open | |
|
| |
03 | Flue Gas Sensor Open | |
|
| |
11 | Water Outlet Sensor Shorted | |
|
| |
12 | Water Inlet Sensor Shorted | |
|
| |
13 | Flue Gas Sensor Shorted | |
|
| |
19, 42, |
| |
45, 46, | Control Failure | |
47, 48 |
| |
|
| |
20 | Flame Detected at Wrong Time | |
|
| |
21 | Polarity Error | |
|
| |
22 | Frequency Error | |
|
| |
24 | Earth Connection Faulty | |
|
| |
30 | Excess Flue Temperature | |
|
| |
31 | Low Water Cutoff Error | |
|
| |
32 | Excess Water Inlet Temperature | |
|
| |
51 | Reset Button Error | |
|
| |
52 | Boiler Model Selection Error | |
|
|
C.WARNING ERRORS:
Indicated by an “H” in the mode display. Operation of the space heating mode is not affected, and the warning is displayed intermittently. Operation of the DHW mode is automatically restored, once the condition is fixed. The temperature display shows the error code. Pressing the “Reset” button is
not required.
B.BLOCKING ERRORS:
Indicated by an “E” in the mode display. Operation is automatically restored, once the condition returns to normal or is fixed. The temperature display shows the error code. Pressing the “Reset” button is not required.
ERROR | INDICATION | |
CODE | ||
| ||
|
|
04Domestic Hot Water Tank Sensor Open
14Domestic Hot Water Tank Sensor Shorted