SMC Networks EX122-SDN1, EX124D/U-SDN1, EX120-SDN1, EX121-SDN1 operation manual Trouble Shooting

Models: EX120-SDN1 EX122-SDN1 EX121-SDN1 EX124D/U-SDN1

1 13
Download 13 pages 33.07 Kb
Page 13
Image 13
6. Trouble Shooting

6. Trouble Shooting

SMC CORPORATION Doc.No.EX##-OME0015

MOD/NET LED

Cause & Countermeasure

Lights off

PWR LED lights off

 

<Countermeasure>

 

Confirm that power for SI unit circuit is supplied.

 

Confirm correct wiring.

 

If above countermeasures do not improve status, please exchange SI unit.

 

PWR LED lights up

 

<Countermeasure>

 

Confirm that baud rate is set correctly.

 

If MOD/NET LED lights off in spite of baud rate is set correctly, change SI unit.

Green flashing

Connection waiting

 

Shows communication waiting status between SI unit and master.

 

<Countermeasure>

 

Confirm master operate correctly.

 

If using scan list, ensure slave is recorded to scan list correctly.

Red flashing

Communication wire disconnected error

 

<Countermeasure>

 

Confirm communication wire is not disconnected.

 

<Remark>

 

Red flashing if master power source is turned off during communication.

Red lights up

Node address overlapping error

 

<Countermeasure>

 

Confirm there is no overlapping on the node address.

 

BUS OFF error

 

Detects communication error.

 

<Countermeasure>

 

Case 1

 

Communication error due to noise.

 

Confirm there is no component or high voltage cable that generate noise

 

around communication wire.

 

Make some distances between communication wire and noise source.

 

Case2

 

Communication cable problem.

 

Confirm terminal resistance (121ohm) connects to the both ends of

 

communication wire that is main wire of communication wire.

 

If red MOD/NET LED is still lights up in spite of above countermeasures,

 

change SI unit.

Manual background CAUTION

When red MOD/NET LED is lit, even if cause is solved, SI unit do not do auto-recovery. In this case, please reset the power to SI unit circuit (Communication/Internal power supply).

SI unit isn’t available for monitoring of power supply for solved valve.

- 13 -

Page 13
Image 13
SMC Networks EX122-SDN1, EX124D/U-SDN1, EX120-SDN1, EX121-SDN1 operation manual Trouble Shooting