SMC Networks EX124D/U-SDN1, EX122-SDN1, EX120-SDN1, EX121-SDN1 operation manual Address setting

Models: EX120-SDN1 EX122-SDN1 EX121-SDN1 EX124D/U-SDN1

1 13
Download 13 pages 33.07 Kb
Page 8
Image 8
3-2. Address setting

SMC CORPORATION

Doc.No.EX##-OME0015

3-2. Address setting

Before setting of address by DIP switch, turn power supply for communication cable in SI unit “OFF”.

Setting (binary) of following items is available by DIP switch installed to cover.

1)Node address (00 to 63)

2)Communication speed (125kbps, 250kbps, 500kbps)

ON

 

 

 

 

 

 

 

 

 

 

 

 

<Setting of node address>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Node

SW1

 

SW2

SW3

 

SW4

SW5

SW6

 

 

address

1

2

4

 

8

16

 

32

 

 

#0

0

0

0

 

0

0

 

0

 

 

#1

1

0

0

 

0

0

 

0

 

 

#2

0

1

0

 

0

0

 

0

 

 

:

 

 

 

 

 

 

 

 

 

 

 

:

 

 

 

 

 

 

 

 

 

 

 

:

 

 

 

 

 

 

 

 

 

 

 

#62

0

1

1

 

1

1

 

1

 

 

#63

1

1

1

 

1

1

 

1

 

<Setting of communication speed>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting

Communication

 

 

 

Max. transmission distance (m)

 

SW7

SW8

 

 

Length of trunk

Length

 

 

 

speed (kbps)

 

Thick

 

Think

of

Total length

 

 

 

 

 

cable

 

cable

branch

 

of

 

 

 

 

 

 

 

 

 

line

branch line

 

0

0

125

 

500

 

100

6

156

 

1

0

250

 

250

 

78

 

0

1

500

 

125

 

 

 

39

 

1

1

Not used

 

 

 

 

Not

used

 

 

Manual background CAUTION

When shipped, node address of 63 and communication speed of 125kbps are set in advance.

When communication error occurs, output condition is cleared.

- 8 -

Page 8
Image 8
SMC Networks EX124D/U-SDN1, EX122-SDN1, EX120-SDN1, EX121-SDN1 operation manual Address setting