
SMA Technol ogie AG Technica l Dat a
Installation Guide SMC50A_60A-IEN073320 Page 89
14.4.3 Country-specific Parameter SettingsSunny Mini Central SMC 5000A
The parameters listed below represent country-specific settings and are only displayed
in installer mode. All other parameters are international and can be viewed in the table
in section 14.4.2.
Parameters designated with * are safety-related grid monitoring parameters. To
change the SMA grid guard parameters, you must enter your personal SMA grid
guard password (Inst.-Code). Call the SMA Serviceline to obtain your personal
SMA grid guard password.
You can see the default settings of the Sunny Mini Central on the name plate (see
section 4.1 "Identification" (Page 12)).
Name Short
descr.
Country settings
Germany Australia Great
Britain
Italy Spain
ACVtgRPro V253 253 253 253 253
Default GER/
VDE0126-1-1
AUS/
AS4777
GB/
G83
IT/
DK5950
SP/
RD1663
dFac-Max Hz/s 40,25 0.2 0.20 2
dZac-Max mOhm 685 20000 350 350 350
Fac-delta- Hz 2,45 0,19 0.5 0.29 0.98
Fac-delta+ Hz 0,19 0,19 0.5 0.29 0.98
I-Ni-Test mA 16000 8000 000
LDVtgC V 0 50 50 50 50
T-Start s10 45 180 10 10
Uac-Min V 198 205 209 198 199
Uac-Max V260 265 261 262 250