Soleus Air KC-30H / KC-35H installation manual Installation in Wall Thicker Than 5 ½inches

Models: KC-30H / KC-35H

1 22
Download 22 pages 16.18 Kb
Page 20
Image 20
Installation in Wall Thicker Than 5 ½inches

Installation in Wall Thicker Than 5 ½inches

The side louvers in outer case provide ventilation to air con- ditioner compressor and fan motor and must not be blocked. When installing unit in a wall over 5 1/2-inches thick, provisions must be made in wall opening to ensure free air flow to the side louvers. This can be accomplished by chamfering the vertical portions of the outside opening as shown.

Ventilation louvers on top of case must not be obstructed. Do not attempt to install unit in walls thicker than

10 1/2-inches.

Front of outercase

¾" minimum projection

5 1/2"

4" Chamfering Walls Thicker Than 5 1/2-inches 223/5" 30 3/5"

10 1/2"

4"

Side air louvers (both sides)

Chamfering Walls Thicker Than 5 1/2-inches

18

Page 20
Image 20
Soleus Air KC-30H / KC-35H Installation in Wall Thicker Than 5 ½inches, Chamfering Walls Thicker Than 5 1/2-inches