◆Install Outdoor Unit

Install Outdoor Unit

Power Cable Connection

1.Remove the handle at the right side plate of the outdoor unit (one screw).

2.Remove the cable clamp, connect the power connection cable with the terminal at the row of connection and make the connection. The fitting line distributing must be consistent with the indoor unit.

3.Use cable clamp to make the cable connection cable.

4.Confirm the fitting lines are properly installed.

5.Install the handle (fixed by one screw).

Notes:

Improper line connection may cause failure of some electrical components and parts

When fixing the cable, a certain degree of play shall be maintained for the cable between the connection point and the fixing point.

Vacuum – Pumping and Leakage Inspection

1.Remove the nut cover at the shutoff valve.

2.Align with the center of the fitting pipe and manually tighten the conical nut sufficiently.

3.Use spanner to tighten the conical nut.

4.Remove the liquid valve cap, the gas valve cap and the nut of refrigerant charging mouth.

5.Use inner hexagon spanner to twist off the liquid valve body and at the same time use screwdriver to open the valve core of the liquid valve. Now gas shall flow out.

6.After gas continues flowing out for about 15 second and refrigerant gas begins to flow out, close the valve core and tighten the nut of refrigerant charge mouth.

7.Completely open the valve body of the liquid valve and the gas valve. See Fig 12

8.Turn and tighten the valve cap, then use soap water or a leak detector to check if there is gas leakage at the outdoor and indoor units and the pipeline connections.

9.If conditions permit, use a vacuum pump to exhaust air in the unit from the valve core. See Fig 13

Draining of Condensate Water of Outdoor Unit

When the air-conditioning unit is in the heating mode, the condensate water generated at the outdoor unit and the water generated by defrosting shall be drained through the drainage pipe to proper place.

Installation methods: As shown in Figure, insert the drainage joint of the outdoor unit into the Φ25 hole on the base plate. Connect the drainage pipe to the drainage mouth so as to drain the condensate water and water generated by defrosting to proper place.

- 20 -

Page 22
Image 22
Soleus Air KFHHP-18-ID, KFHHP-18-OD Install Outdoor Unit, Power Cable Connection, Vacuum - Pumping and Leakage Inspection