ELECTRICAL REQUIREMENTS
For 50 Pound (22 kg) Tumblers
REQUIREMENTS
Heat Source | Electrical Specs | Wires Required and Terminal Block Connection | |||
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
Gas & Steam | 230/50/1 | L1 | L2 |
| Ground to PE Busbar |
|
|
|
|
|
|
Steam | L1 | L2 | L3 | Ground to PE Busbar | |
|
|
|
|
|
|
Electric | 230/50/1 | L1 | L2 |
| Ground to PE Busbar |
|
|
|
|
|
|
Electric | L1 | L2 | L3 | Ground to PE Busbar | |
|
|
|
|
|
|
Reversing Models |
|
|
|
|
|
|
|
|
|
|
|
Gas & Steam | 230/50/1 | L1 | L2 |
| Ground to PE Busbar |
|
|
|
|
|
|
Gas & Steam | L1 | L2 | L3 | Ground to PE Busbar | |
|
|
|
|
|
|
Electric | 230/50/3 | L1 | L2 | L3 | Ground to PE Busbar |
|
|
|
|
|
|
Electric | L1 | L2 | L3 | Ground to PE Busbar | |
|
|
|
|
|
|
Figure 11
GAS AND HIGH PRESSURE STEAM DRYING TUMBLER
GAS AND HIGH PRESSURE STEAM DRYING TUMBLERS
| 208V / 240 V | 208 / 240 V | 380 / 415 V |
| 1 Phase, 50 Hz. | 3 Phase, 50 Hz. | 3 Phase, 50 Hz. |
|
|
|
|
Minimum Wire Size | 14 AWG (2.081 mm²) | 14 AWG (2.081 mm²) | 14 AWG (2.081 mm²) |
|
|
|
|
Circuit Breaker | 15 AMP | 15 AMP | 15 AMP |
|
|
|
|
Poles | 2 | 3 | 3 |
|
|
|
|
Figure 12
ELECTRIC DRYING TUMBLERS
NOTE: DO NOT use aluminum wire.
ELECTRIC DRYING TUMBLERS
| 240 V, 3 Phase | 380 V, 3 Phase | 415 V, 3 Phase |
| 50 Hz. | 50 Hz. | 50 Hz. |
|
|
|
|
Minimum Wire Size | 3 AWG (26.67 mm²) | 6 AWG (13.32 mm²) | 6 AWG (13.32 mm²) |
|
|
|
|
AMP Rating | 78 AMP | 48 AMP | 45 AMP |
|
|
|
|
Circuit Breaker | 80 AMP | 50 AMP | 50 AMP |
|
|
|
|
Poles | 3 | 3 | 3 |
|
|
|
|
Figure 13
38 | M412616 |