Installation/Operation Supplement
Position and Level the Tumbler
WARNING
To reduce the risk of severe injury, clearance of tumbler cabinet from combustible construction must conform to the minimum clearances.
W056
1 | 2 | 3 |
|
| 4 |
5
6
7 TMB2020N
8
TMB2020N
NOTE: Shaded areas indicate adjacent structure.
113 mm (0.5 in.) recommended between machines for removal or installation.
2Allow
3102 mm (4 in.) maximum header thickness
4Minimum clearance permitted for remainder: Gas 102 mm (4 in.), Steam 305 mm (12 in.)
5Guard
6Provision for
7610 mm (24 in.) minimum, 914 mm (36 in.) recommended for maintenance purposes
86 mm (0.25 in.) recommended for removal or installation purposes, zero clearance allowed
Figure 112 | © Published by permission of the copyright owner – DO NOT COPY or TRANSMIT | M414881 (EN) |