Operation
Caution
Model | Coil Volume | Model | Coil Volume | |
US Gallons | US Gallons | |||
|
| |||
|
|
|
| |
MHF702__061 | 65 | MHF705__061 | 235 | |
|
|
|
| |
MHF702__081 | 85 | MHF705__081 | 315 | |
|
|
|
| |
MHF702__101 | 105 | MHF705__101 | 390 | |
|
|
|
| |
MHF702__121 | 125 | MHF705__121 | 465 | |
|
|
|
| |
MHF702__062 | 75 | MHF705__062 | 285 | |
|
|
|
| |
MHF702__082 | 100 | MHF705__082 | 380 | |
|
|
|
| |
MHF702__102 | 120 | MHF705__102 | 470 | |
|
|
|
| |
MHF702__122 | 150 | MHF705__122 | 565 | |
|
|
|
| |
MHF703__061 | 85 | MHF706__061 | 390 | |
|
|
|
| |
MHF703__081 | 115 | MHF706__081 | 500 | |
|
|
|
| |
MHF703__101 | 140 | MHF706__101 | 610 | |
|
|
|
| |
MHF703__121 | 170 | MHF706__121 | 725 | |
|
|
|
| |
MHF703__062 | 100 | MHF706__062 | 475 | |
|
|
|
| |
MHF703__082 | 130 | MHF706__082 | 610 | |
|
|
|
| |
MHF703__102 | 165 | MHF706__102 | 750 | |
|
|
|
| |
MHF703__122 | 200 | MHF706__122 | 885 | |
|
|
|
| |
MHF704__061 | 160 | MHF707__061 | 450 | |
|
|
|
| |
MHF704__081 | 210 | MHF707__081 | 580 | |
|
|
|
| |
MHF704__101 | 260 | MHF707__101 | 710 | |
|
|
|
| |
MHF704__121 | 310 | MHF707__121 | 840 | |
|
|
|
| |
MHF704__062 | 190 | MHF707__062 | 570 | |
|
|
|
| |
MHF704__082 | 250 | MHF707__082 | 740 | |
|
|
|
| |
MHF704__102 | 315 | MHF707__102 | 905 | |
|
|
|
| |
MHF704__122 | 375 | MHF707__122 | 1071 | |
|
|
|
|
When the use of industrial antifreeze solutions is not possible, the system must be operated to meet both of the following conditions.
1.Maintain sufficient flow rate through the coil.
2.Maintain sufficient heat load on the process fluid. Fluid exiting the coil must be maintained at or above 45°F. Cycling of the recirculation pump should not be used to control process temperatures.
Draining the coil is not acceptable as a normal method of freeze
It is recommended that you discuss your freeze prevention options with your local Marley sales representative.