Bushing Fastener Torque Values
Warning
Warning
Maintenance
Bushing | Fastener | Torque ft·lbƒ | |
|
|
| |
SH | 1⁄4 - 20 | 6 | |
SDS | 1⁄4 | - 20 | 6 |
SD | 1⁄4 | - 20 | 6 |
SK | 5⁄16 | - 18 | 13 |
SF | 3⁄8 | - 16 | 22 |
E | 1⁄2 | - 13 | 35 |
F | 9⁄16 | - 12 | 65 |
Fluid Cooler Maintenance
Some maintenance procedures may require maintenance personnel to enter the fluid cooler. Each cased face of the fluid cooler has a door for access to the interior of the tower.
The optional fan deck
The purchaser or owner is responsible for providing a safe method for entering or exiting the access door. Use of the fan deck ladder to enter or exit the access doors may result in a fall.
Included with this instruction packet are separate User Manuals on each major operating component of the tower, and it is recommended that you read them thoroughly. Where discrepancies may exist, the separate User Manuals will take precedence.
The following is recommended as a minimum routine of scheduled main- tenance:
Always shut off electrical power to the tower fan motor prior to performing any inspections that may involve physical contact with the mechanical or electrical equipment in or on the tower. Lock out and tag out any electrical switches to prevent others from turning the power back on. Service personnel must wear proper personal protective clothing and equipment.
➠
25