State Industries SEV-150 THRU SEV-10000 instruction manual Control System Menus, Menus Description

Models: SEH-200 THRU SEH-10000 SEV-150 THRU SEV-10000

1 24
Download 24 pages 48.09 Kb
Page 11
Image 11

 

TABLE 3 - CONTROL SYSTEM MENUS

 

 

MENUS

DESCRIPTION

Temperatures

Most commonly accessed menu. Operating Set Point, Differential settings, Tank Temperature and Tank Probe

Offset are located in this menu.

 

 

 

Heater Status

Current Operating State/Mode (heating/standby etc) and status (open/closed - on/off - yes/no) of monitored

water heater functions and components are displayed in this menu.

 

 

 

Economy Mode Setup

Seven day 24 hour time clock with temperature set back capability to reduce operating costs during unoccupied

or reduced demand periods.

 

 

 

 

The control system’s CCB (Central Control Board - see wiring diagrams) features on board SPDT (single pole

Alarm Output Setup

double throw) relay contacts for building EMS (Energy Management System) notification of operational conditions

such as Fault Conditions and heating mode status. This menu features a list of user definable conditions for

 

 

relay activation.

Display Settings

Temperature units (°F or °C), appearance (brightness contrast) and backlight delay user adjustable settings are

located in this menu.

 

 

 

Heater Information

Elapsed time of operation, total heating cycle time, heating cycle count, heating element(s) cycle count and on

time along with UIM and CCB software revisions can be viewed in this menu.

 

 

 

Current Fault/Alert

Displays any current Alert or Fault messages.

 

 

 

Retains 9 event history of Fault/Alert messages with time stamp. The Fault History is useful when dealing with

Fault History

intermittent operational problems or when the customer has reset the control system prior to a service agent’s

 

arrival.

 

 

 

Total accumulated number each individual Fault condition has occurred is displayed in this menu. This

Fault Occurrence

running total of Fault Occurrences can be useful in determining which (if any) operational problems have been

 

persistent.

 

 

Restore Factory Defaults

This control system feature allows the user to restore control system user settings to their factory default settings.

Alarm Output Setup and Display Settings menu items ARE NOT changed when factory defaults are restored.

 

 

 

Accessible by pressing the corresponding Operational Button from most menus and screen displays. This menu

Help Menu

provides access to instructions and explanations for user settings, Operating States, Status Icons, manufacturer’s

 

web address, technical support phone number and service agent contact information.

 

 