4 | Installation |
|
|
4-1 Installing the SCC1-5Q Control Panel
Note: Before you mount the panel, consider how you run wiring to the vacuum receivers, the filter chamber atmospheric valve (if so equipped) and the pump motor starter(s), vacuum switch(es), and vent valve(s).
Mount the panel on a flat, vertical area. It should be a visible area that gives your operator access to the control. The panel requires a low voltage power drop as listed on the serial tag.
4-2 Making Electrical Connections
Refer to local electrical codes, the schematic and connection diagrams supplied with this unit and the serial tag for wiring considerations. Run all wiring in conduit if codes require it.
4-3 Making SSC1-5Q Control Panel Power Drop Wiring Connections
Hardwire the input power at
Important! Sterling recommends that you protect PLC memory by providing the control panel with a dedicated circuit, a true earth ground, and a spike/surge protector.
4-4 Connecting the Control Panel to Vacuum Receivers
1.On 24 VDC control voltage systems, run a common +24 VDC wire and a common 0 (zero) VDC wire from the controller to each vacuum receiver in the SSC system.
2.On all systems, run two wires to each vacuum receiver: one each from the controller to the
3.Make sure that the solenoid and the proximity switch (if supplied) on vacuum receivers are the same voltage (24
Page 19 of 38