Sterling 882.00291.00 Proc Blwr, High Temp, Alarm Message, Cause, Corrective Action, Dryer Status

Models: 882.00291.00

1 52
Download 52 pages 3.6 Kb
Page 38
Image 38

Alarm Message

Cause

Corrective Action

Dryer Status

 

 

 

 

HIGH TEMP

The process

The process heater

- Dryer Shuts down:

 

temperature has

contactor has failed in the

- Process blower OFF.

 

exceeded the alarm

closed position. Check

- Process heaters OFF.

 

set point.

heater contactor, replace if

- Regen heaters OFF.

 

The high temperature

necessary.

- Alarm light is ON

 

snap switch of the

 

- Alarm horn is ON.

 

Check the Process Heater

 

process heater box

box high temperature snap

 

 

has tripped.

switch, replace if necessary

 

 

 

The Regeneration heater

 

 

 

contactor has failed in the

 

 

The high temperature

 

 

snap switch on of the

closed position. Check

 

 

regeneration heater

heater contactor, replace if

 

 

boxes has tripped

necessary.

 

 

Check the high temperature

 

 

 

 

 

 

snap switches on the

 

 

 

regeneration heater

 

 

 

mounting plates, replace if

 

 

 

necessary.

 

PROC BLWR

The process blower

Make sure the process air

 

 

pressure switch did not

filter is clean. Clean or

 

 

detect enough

replace if necessary.

 

 

pressure.

 

 

 

Check the rotation of the

 

 

Process blower

blower.

 

 

overload has tripped.

 

 

 

Check the pressure switch

 

 

Process blower motor

 

 

hose connection. Replace

 

 

has failed.

 

 

hoses or the pressure

 

 

 

 

 

 

switch.

 

 

 

Check the over load rating

 

 

 

against the wiring diagram.

 

 

 

Adjust accordingly.

 

 

 

Check the wiring of the

 

 

 

blower. Make sure it is wired

 

 

 

for the proper voltage.

 

 

 

Check the process blower

 

 

 

fuses for any fault. Replace

 

 

 

if necessary.

 

 

 

Check the blower motor

 

 

 

starter. Replace if

 

 

 

necessary.

 

 

 

Check the blower motor.

 

 

 

Replace if necessary.

 

 

 

Check the incoming voltage

 

 

 

against the name plate of

 

 

 

the dryer.

 

 

 

 

 

15, 30, & 60 cfm Compact Dryers

38

Page 38
Image 38
Sterling 882.00291.00 specifications Proc Blwr, High Temp, Alarm Message, Cause, Corrective Action, Dryer Status