Sterling STT 1600 operating instructions STT 5.6.1. Resetting the control values, Maintenance

Models: STT 1600

1 89
Download 89 pages 41.29 Kb
Page 58
Image 58
STT 1600

STT 1600

5.6.1. Resetting the control values

»

&

This electrical work is intended to be carried out only by trained personnel.

After changing the battery or the PLC the control values should be reset- ted.

All control values are set back to the standard settings.

Open the control box with the switch box key which is part of the supply. Turn the key to the STOP position.

Turn the key to the MRES position.

Hold the key in this position until the STOP-LED comes on for the second time and remains on (this takes 3 seconds).

Turn the key to the STOP position.

Within 3 seconds you must turn the switch back to the MRES position.

Hold the key until the STOP-LED flashes.

&

When the CPU has completed the reset, the STOP-LED stops flashing and remains lit.

Close the control box.

SM2-630

Maintenance 5-13

Page 58
Image 58
Sterling STT 1600 operating instructions STT 5.6.1. Resetting the control values, Maintenance