Sterling TF-125, TF-400, TF-150, TF-300, TF-200, TF-350 Tubular Unit Heater High Altitude Deration

Models: TF-100 GF-150 GF-250 GF-400 TF-125 TF-250 TF-175 TF-350 TF-200 TF-300 TF-150 TF-400

1 28
Download 28 pages 32.25 Kb
Page 19
Image 19

TUBULAR UNIT HEATER

HIGH ALTITUDE DERATION

This Tubular Unit Heater has been manufactured utilizing standard burner orifices and a normal manifold pressure setting as per the specifications shown on your unit rating plate.

All unit deration must be done through field adjustments by a qualified technician. Once the proper adjustments are made in the field, attach label #J17-06459 to the unit, and record adjusted manifold pressure, altitude of the unit installation and the technician’s name and date on the label using a permanent marker.

Refer to Installation Instruction section on Adjustments- Gas Input Rate for adjusting the manifold pressure.

Table 5A

 

 

NATURAL GAS

PROPANE (LP) GAS

 

 

 

 

 

 

 

 

Heating*

Manifold

Heating*

Manifold

Altitude

Value

Pressure

Value

Pressure

(Feet)

BTU/Cu. ft.

(In. W.C.)

BTU/Cu. ft.

(In. W.C.)

 

 

 

 

 

 

2,000

 

948

3.5

2,278

8.6

 

 

 

 

 

 

2,500

 

931

3.5

2,237

8.5

 

 

 

 

 

 

3,000

 

914

3.3

2,196

8.4

 

 

 

 

 

 

3,500

 

897

3.2

2,156

8.4

 

 

 

 

 

 

4,000

 

881

3.2

2,116

8.3

 

 

 

 

 

 

4,500

 

865

3.2

2,077

8.2

 

 

 

 

 

 

5,000

 

849

3.1

2,039

8.1

 

 

 

 

 

 

5,500

 

833

3.1

2,000

8.0

 

 

 

 

 

 

6,000

 

818

3.0

1,964

7.9

 

 

 

 

 

 

6,500

 

802

3.0

1,927

7.7

 

 

 

 

 

 

7,000

 

787

2.9

1,891

7.6

 

 

 

 

 

 

7,500

 

771

2.9

1,853

7.5

 

 

 

 

 

 

8,000

 

756

2.8

1,817

7.4

 

 

 

 

 

 

8,500

 

741

2.8

1,781

7.2

 

 

 

 

 

 

9,000

 

726

2.7

1,745

7.1

 

 

 

 

 

 

9,500

 

711

2.7

1,709

6.9

 

 

 

 

 

 

10,000

 

696

2.6

1,673

6.8

 

 

 

 

 

 

*Notes:

1.Consult local utility for actual heating value.

2.Tables based on heating value of 1,050 BTU/Cu. ft. at sea level.

19

Page 19
Image 19
Sterling TF-125, TF-400, TF-150, TF-300, TF-200, TF-350, TF-175, TF-250, GF-400, GF-250 Tubular Unit Heater High Altitude Deration