ERROR CONDITION CODE 09

Error 09 conditions are usually caused by insufficient cooling at the freezer's condenser. If the control panel displays a High Pressure Cutout error (Error Code 09), turn the freezer power off. Press the High Pressure Cutout Reset Switch located on the upper, left hand corner of the left side panel. There is a round, black boot covering the reset switch. Pressing in the center of the boot will reset the switch.

In air cooled condenser models, check the air filter to make sure it is clean (see section 4.6). Replace the filter as required. Check for proper air clearance around the freezer. The freezer must have a minimum of 3" (7,5cm) of space on all sides and 10" (25cm) at the top for proper circulation. A minimum of 6" (15cm) clearance is required in high ambient conditions.

On water cooled condenser models, check for proper waterflow through the condenser coil. After the cause of the error is determined and corrected, turn on the Main Freezer Power Switch and place the Freezing Cylinder switch to the on position. If the Control Panel still displays the error condition code, call your Authorized Stoelting Distributor for further assistance.

ALTERNATINGFLASHINGCONTROLPANELLIGHTS

When the Main Freezer Power Switch is placed in the ON position and the left Freezing Cylinder OFF/ON switch is left in the OFF position, the green and amber control panel lights will flash in alternating sequence. This indicates that the storage cabinet is being refrigerated, but the left freezing cylinder is not receiving power. Placing the left Freezing Cylinder OFF/ON switch in the ON position will return the freezing cylinder to the SLEEP mode. Pressing the PUSH TO FREEZE button will begin the freezing cycle.