SITE REQUIREMENTS

2. FLUE OUTLET POSITIONS

IMPORTANT: Seek specialist advice if installing in a dwelling with a thatched roof

Terminal

Flue

Horizontal

Measurement

Vertical

Measurement

150mm

max

Insulation

Adjacent Building

 

 

The vertical measurement is the lowest from either the

 

 

point of discharge or 150mm above insulation.

 

 

 

 

Position On Roof

Minimum Clearances

 

 

 

A

On ridge or within 600mm

600mm above ridge

B

Elsewhere on roof

2300mm horizontally from roof surface and:

 

 

a) 1000mm above highest point of flue exit from roof or b) as high as the ridge

C

On pitched, within 2300mm horizontally to

1000mm above top of opening

 

openable window, dormer

 

D

Within 2300mm of another building

600mm above top of building

3. Minimum dimensions - HEARTH

1

150

225 500

Superimposed Hearth (or area to be free of combustible material)

150Constructional

Hearth

A

3.1

The appliance must stand on a non-combustible

 

constructional hearth which is at least 125mm thick with

 

the minimum dimensions as shown in diagram. If it is to be

 

fitted in a raised setting consideration may need to be given

 

to extending the depth of the hearth to safely containing

 

any falling logs or embers.

3.2

The building must have a suitable load-bearing capacity for

 

the hearth and appliance.

 

• Consult a structural engineer for advice before

 

proceeding

3.3

When fitting into an existing hearth check:

 

• That the appliance complies with current construction

 

regulations and is at least the minimum sizes shown

3.4

If there is no existing fireplace or chimney it is possible to

Dimension

A

 

 

16"

720

 

 

22"

870

24"

920

26"

970

28"

1020

 

construct a suitable non-combustible housing and hearth

 

setting. The flue must be installed in accordance with all

 

local and national regulations and current rules in force.

 

• Check if adding a new chimney to your property requires

 

planning permission

3.5

Some houses are built using a timber frame construction

 

with high levels of thermal insulation. Isolate the appliance

 

from combustible materials, and provide sufficient

 

ventilation to maintain the heating efficiency.

15

Page 15
Image 15
Stovax Open Log Burning Convector Fireboxes manual Flue Outlet Positions, Minimum dimensions Hearth