Installation - Electrical Requirements
It is recommended that a licensed electrician install the power to your spa, in accordance with the National Electric Code or any local electrical codes in effect at the time of installation.
The circuit breaker must be dedicated and cannot be shared with any other appliances. It should be labeled and easily accessible to users. DO NOT USE EXTENSION OR PLUG- TYPE CORDS OF ANY KIND. The use of a
Metal surfaces within 5 feet of the spa must be grounded to the spa.
A 120 Volt - 20 Amp GFI rated plug is furnished with the Antigua Silver Spa.
CAUTION: This spa will not work if more than one GFCI is used on the circuit. On 220 Volt applications,
power supply must be hard wired into the power pack.
110/220 Volt Antigua
Electrical Connections:
TERMINAL
BLOCK
Two Wire Live (black) Hot Black
& Ground | Neutral (white) Neutral |
| |
| Hot Red |
Ground (copper or green)GRD
Note: Your Cyprus Spa’s Heater can be converted to 220 Volts. The Spa’s pump will remain 120 Volts.
This change must be performed by a certified electrician.
220 Volt Antigua
Electrical Connections:
To convert spa from 120 volt to 220 Volt remove white jumper wire from J11 and J32.
Next, move move dip switch 10 to the off position
| Three Wire |
|
|
|
|
| |
|
|
|
|
| TERMINAL | ||
| & Ground |
|
|
|
| ||
|
|
|
|
| BLOCK | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Live (black) Hot |
| ||||
|
|
|
|
|
|
| |
|
|
|
|
| |||
|
| Live (red) Hot |
| ||||
|
|
|
|
|
|
| |
|
| Neutral (white) N |
|
Ground (copper or green)GRD
These wires go to the PC Board Control Circuit.
Connections should be made using copper conductors only. The connecting wire and circuit breakers or fuses must be sized to accommodate the total ampere load as specified on the equipment module data label.
Strong Pools and Spas only makes electrical recommendations, always consult a certified electrician.
4