3.5Cabling/wiring
Connecting of the COMPACT is a very important step in the installation. You must take care that all connecting work is carried out in a clean and correct manner and under no circumstances that a cable is connected to a wrong terminal.
Connecting of the COMPACT must be carried out in the following order. In case of dismantling this order must be reversed.
3.5.1Pre-installation settings
Before you start with the cabling of the COMPACT you must set the type of battery. In case that
3.5.2Connection to battery
Get the batteries ready for connection: Matching battery terminals, matching fuse on a clamp. Prepare battery cables, if necessary press on cable tabs/shoes. Connect red cable on
On connecting the battery the COMPACT needs 1 – 2 Minutes to calculate the actual capacity of the battery. During this time the battery condition is shown as 100% charged. (LED 14 – 17 lit).
If the LED 12 Battery Low/High is lit, the battery charge is too low. If the LED 12 Battery Low/High is blinking, the battery charge is too high.
Caution: With a wrong battery voltage the COMPACT can be destroyed. ( For example:
connecting a C1312 to a 48V-Battery).
Nevertheless. if the COMPACT had been connected with reverse polarity, it is highly probable that the fuse inside the casing is defect. Before opening the casing cover all terminals must be disconnected including the battery. If the COMPACT does not function after the changing of the fuse and correcting of the polarity, it means that it is defect and must be sent for repair.
3.5.3Connection the 230Vac-Consumer Device (AC OUTPUT)
The 230V consumer device must be connected to the screw terminal AC OUTPUT. For this, use a
Caution: High tension can by there. By sure that’s the compact is turn off (LED 13 alight)
before the connection.
3.5.4Connection the 230Vac Input (AC INPUT)
The